Feeder Reconfiguration for Loss Reduction Under Transformer Constraints

  • Chenfan Power

Short answer

Feeder reconfiguration loss reduction moves normally open points so that load is shared more evenly between feeders. Because resistive losses scale with the square of current, two feeders carrying equal loads lose less than the same total carried unequally. In an illustrative pair of 11 kV feeders carrying 6 MW and 2 MW with 0.5 Ω lumped resistance per phase each, losses are about 165 kW; moving the open point so each carries 4 MW reduces them to about 132 kW. The new configuration must remain radial, use only permitted switches and supply paths, and keep every substation transformer, distribution transformer and line within its limits. Voltage at the ends of the reconfigured feeders also changes and must be checked. Loss-driven reconfiguration is a planning or operational optimisation and should not be confused with fault restoration logic.

Table of feeder reconfiguration loss reduction example
Illustrative losses before and after balancing two 11 kV feeders

Why balancing reduces losses

Illustrative losses before and after balancing two 11 kV feeders
CaseFeeder 1Feeder 2Losses
Before6 MW, 315 A2 MW, 105 A≈ 165 kW
After4 MW, 210 A4 MW, 210 A≈ 132 kW

Ploss = 3 I^2 R

Illustrative example. Two 11 kV feeders with lumped resistance 0.5 Ω per phase each; loads 6 MW and 2 MW at unity power factor. Values chosen for demonstration.

Currents: 6,000 / (1.732 × 11) ≈ 315 A and ≈ 105 A.

before ≈ 3 × 0.5 × (315^2 + 105^2) ≈ 165 kW

After moving 2 MW: both ≈ 210 A.

after ≈ 3 × 0.5 × 2 × 210^2 ≈ 132 kW

Savings of about 33 kW, 20 %. Real feeders have distributed loads, so savings are calculated by load flow.

Constraints

ConstraintCheck
Radial topologyNo loops, every load supplied once
Permitted switchesOnly switches approved for routine operation
Substation transformerLoading of receiving transformer, including emergency margin
Distribution transformersUnchanged load, but voltage changes
Lines and cablesThermal ratings
VoltageEnd-of-feeder limits
ProtectionSettings valid for new topology; see adaptive protection when a feeder is reconfigured

Transformer losses

Feeder reconfiguration need not change the customers assigned to each distribution transformer, but changed terminal voltage can change current and losses. Recalculate loss duty where voltage, tap or excitation changes; do not assume every distribution-transformer loss remains fixed. Substation transformer load losses change with feeder allocation and should be included. Loss accounting at transformer level is covered in technical and nontechnical losses at a distribution transformer.

Model quality

  1. Switch states in the model must match the field; hidden parallels distort results; see normally open points without hidden parallel sources.
  2. Load allocation to transformers should be calibrated; see calibrating transformer load allocation with AMI data.
  3. Time variation: the best configuration at peak may not be best over a year; time-series studies help; see quasi-static time-series studies.

Separate from restoration

Fault restoration uses different objectives and time limits. A configuration chosen for losses must still allow restoration options, but the two analyses are separate.

Where this reasoning stops. Lumped resistance oversimplifies; savings come from load flow over representative periods.

Practical takeaway

Evaluate reconfiguration options with load flow over time, accept only radial permitted topologies, check every transformer and line against limits, and recheck voltages and protection before adopting the change.