A DC smoothing reactor limits current variation in the DC circuit; HVDC pole and return arrangements determine its relation to earth. [1] A small terminal difference can therefore coexist with high terminal-to-earth potentials. Assess both boundaries under each specified station condition.
Define simultaneous terminal voltages v1 and v2 against the same earth reference. Differential voltage is vd = v1 − v2; the common-mode coordinate is vc = (v1 + v2)/2, in volts. Actual insulation paths still use their endpoint voltages, not the average coordinate alone. [2]

Map each path to its driving voltage
| Insulation path | Driving quantity | Geometry needed |
|---|---|---|
| Between reactor terminals or winding sections | Differential and internal distributed response | Winding geometry and transient parameters |
| Terminal lead to earth | Each terminal’s earth potential | Lead, shield and support layout |
| Coil support to earth | Local conductor potential relative to support reference | Solid insulation and surface path |
| Nearby station structure | Actual potential and coupling | Grounding and connection model |
Keep the station earthing scheme in the case
Neutral location, pole configuration and connected arresters or capacitances affect earth-referenced voltages. A shift assumed for one scheme cannot be transferred to another without rebuilding the network. Specify fault location and clearing behavior along with the waveform.
The inductive relation vd ≈ L di/dt can help explain the differential voltage for a simplified linear reactor. Here L is in henries, i in amperes and t in seconds, giving differential voltage in volts. It does not calculate the common-mode earth potential. That comes from the station network.
Keep each earth-referenced terminal waveform on the same time axis as the differential waveform, particularly during a pole voltage shift.
Calculate differential and earth-referenced stress
Assumptions: at one specified transient instant the terminals are +20 kV and +15 kV to earth; the project’s corresponding operating-stress ceilings are 6 kV terminal-to-terminal and 18 kV for either terminal to earth. Differential stress is 5 kV and passes by 1 kV. Common mode is 17.5 kV, but the +20 kV terminal exceeds its earth ceiling by 2 kV. Hold the insulation assignment: neither the 5 kV difference nor the 17.5 kV average proves earth-path compliance. These are assumed operating-stress gates, not standardized test levels. [2]
References
- A. Alassi, S. Bañales, O. Ellabban, G. Adam and C. MacIver, HVDC Transmission: Technology Review, Market Trends and Future Outlook, Renewable and Sustainable Energy Reviews 112, 2019, sections 3.1–3.2. DOI: 10.1016/j.rser.2019.04.062.
- U.S. Department of Energy, DOE-HDBK-1011/3-92, Electrical Science, Volume 3, June 1992.