Build a calibrated axial-force channel on the instrumented tie bolt and retain its known-force reference. Check bending, apparent temperature response and zero history so each assembled reading has a defined force meaning and uncertainty.
Calculation basis. Numerical demonstrations use editorial assumptions unless a value is expressly attributed to a cited supplier, standard or published study. Dimensions describe the stated model geometry; test results introduced with “assume” or “suppose” are hypothetical inputs. Calculated outputs inherit those conditions.
Define which bolt section is measured, which force is being inferred and how the sensor installation is qualified for the actual bolt. The measurement does not, by itself, establish the pressure distribution reaching the core packets.
Calibrate the instrumented bolt rather than a nominal drawing
For an ideal elastic uniaxial section, F = EAε relates force and mechanical axial strain. Using it directly assumes the relevant modulus, effective area and local strain state. A thread, hole, section change, eccentric load or sensor installation can make a nominal-area calculation unsuitable for the measured location.
Build the force relationship from an appropriate reference force applied to the actual instrumented configuration or a justified equivalent. Record the force reference, sensor and amplifier settings, loading geometry, temperature and the permitted elastic range. Include repeated loading and unloading so zero return, hysteresis and repeatability remain visible.
Pirnat, Čepon and Boltežar’s original laminated-stack study measured bolt-stem deformation with strain gauges to establish its experimental torque-to-clamping-force relationship. That is useful evidence for measuring force rather than assuming torque is force. Its particular calibration and test pressures are not transferable production settings. [2]
Qualify the HBM sensor installation geometry and its temperature compensation for the actual screw. Approve any modified bolt and installation against the required mechanical and environmental conditions.
Separate axial strain from bending in the chosen arrangement
An ideal matched pair of axial surface gauges at diametrically opposite points can be used to distinguish mean axial strain from a bending contribution. For a linear elastic section with the stated geometry:
ε_1 = ε_a + ε_b + ε_T;
ε_2 = ε_a − ε_b + ε_T.
Here ε_a is axial mechanical strain, ε_b is the bending strain at the first gauge, and ε_T represents a common apparent thermal contribution in this simplified illustration. After individual offsets are dealt with, the mean is ε_a + ε_T and the half-difference is ε_b.
Averaging these two readings cancels the ideal antisymmetric bending term. It does not cancel a common apparent thermal term. Unequal placement, gauge factors, local geometry or temperature gradients can also prevent the intended separation. This paired-channel example is not the wiring diagram of the HBM cylindrical sensor.
Apparent thermal strain, lead resistance, gauge-factor variation, adhesive behaviour and mechanical temperature response can alter the force indication. Characterize the complete installed measurement chain against an independent force and temperature reference.
A declared calibration example makes the corrections visible
Use the following hypothetical reference calibration for the compensated axial channel:
| Compensated axial strain | Reference force |
|---|---|
| 0 µε | 0 kN |
| 500 µε | 5 kN |
| 1000 µε | 10 kN |
The illustrative slope is C = 0.010 kN/µε with zero intercept. These points are hypothetical, not measured calibration data or a permissible bolt load range.
Now suppose two individually zero-corrected channel outputs are 620 and 480 µε. Their mean is 550 µε, and half their difference is 70 µε. Assume an independently characterized common apparent thermal correction of 30 µε under this particular condition.
The corrected axial strain is 550 − 30 = 520 µε, giving F = 0.010 × 520 = 5.20 kN in the assumed calibration. The 70 µε term belongs to the simplified bending indicator, not an extra axial force to add. A real calibration must retain the actual intercept, nonlinearity and uncertainty instead of forcing these ideal values.

Correct apparent temperature response without removing real force changes
Apparent thermal strain, lead resistance, gauge-factor variation, adhesive behaviour and mechanical temperature response can alter the force indication. Characterize the complete installed measurement chain against an independent force and temperature reference.
Determine the temperature response of the actual installation and acquisition chain in a suitable no-force-change condition. Account for the channel arrangement, leads, adhesive and gauge-to-bolt strain transfer. A material-matched gauge can reduce apparent strain while leaving a residual error.
A temperature change can also alter the real bolt force through the constrained assembly. That is a mechanical result to retain. Subtracting every temperature-correlated signal as an instrument error could remove the quantity the study needs to observe. Separate the characterized apparent response from actual thermally induced load using the physical reference and calibration evidence.
Preserve the reference through assembly and inspection
Record unloaded or known-force zeros before installation at a stated temperature. Track any permitted change to the gauge, wiring, amplifier or bolt position. Once the bolt carries preload, electronically setting its output to zero removes the original absolute-force reference unless a justified new known-force reference is established.
An after-assembly reading therefore needs its zero history and temperature state. A later unloaded zero-return check can reveal offset change or permanent effects, but a non-returning zero does not alone identify whether the cause is bolt plasticity, sensor drift or the installation. Investigate within the actual measurement design.
Deliver the calibrated force with its uncertainty, valid range, channel arrangement and zero history. Assess its transfer into core pressure through the actual clamp and contact load path as a separate assembly calculation.
Size an independent force check from the steel inventory
Nippon Steel lists 23ZH90 at a nominal steel thickness of 0.23 mm and an assumed density of 7.65 kg/dm³. [1] An assumed 500-sheet, 300 × 500 mm packet contains 131.9625 kg of nominal steel and weighs 1.29455 kN at the assumed g = 9.81 m/s². Using that force as an assumed calibration-check load with C = 0.010 kN/µε predicts 129.46 µε. The calibration fixture must transfer that load axially through the instrumented bolt. Compare the measured indication against the reference force; packet weight is a calibration input only when its load path is established.
Manufacturing controls. Control the bolt gauge location, bending rejection, thermal compensation, force-reference uncertainty and the installed zero. Keep clamp preload distinct from the weight used in this illustrative calibration check. [2]
The NASA joint analysis treats bolt/member compliance, thermal mismatch and contact seating as separate contributors to preload. Retain that complete load path in the assembly model. [3]
References
[1] Nippon Steel Corporation, Grain-Oriented Electrical Steel Sheets, undated, specification tables and annealing compatibility.
[2] M. Pirnat, G. Čepon and M. Boltežar, Introduction of the linear contact model in the dynamic model of laminated structure dynamics: an experimental and numerical identification, 2013, DOI 10.1016/j.mechmachtheory.2013.02.003.
[3] J. A. Chambers, Preloaded Joint Analysis Methodology for Space Flight Systems, NASA TM-106943, 1995.