Platform, tank, electrode and measurement capacitances draw current at different nodes of a cascade stack. Finite stage impedances convert those currents into unequal voltage drops. Solve the driven stack with its actual capacitance and source arrangement.
HIGHVOLT describes cascades with elevated insulated frames and intermediate-stage equipment. The electrical model must retain the potentials and loads of those actual structures rather than represent only the final test-object capacitance. [1]

Build a capacitance-node equivalent
Label each driven stage node and each conductive platform whose potential is defined by the approved arrangement. Include capacitance from a node to ground and between relevant nodes. Mutual capacitive current depends on the voltage difference between the two nodes, not on either node’s absolute voltage alone.
For a sinusoidal analysis, the current through capacitance Ckj from node k to node j is jωCkj(Vk − Vj). A ground capacitance uses Vj = 0. Connect these branches to the stage source and impedance representation.
| Capacitive branch | Driving voltage | Why its location matters |
|---|---|---|
| Platform to ground | Platform potential | Adds a shunt current at that elevation |
| Between platforms | Difference between their potentials | Loads two nodes with equal and opposite branch currents |
| Top electrode to surroundings | Local conductor-potential differences | Changes the terminal load and field distribution |
| Divider or coupling equipment | Its actual connection voltage | Cannot always be assigned entirely to the test object |
Model the driven stack and its distributed capacitance
Each transformer stage actively contributes voltage. A passive capacitor-divider equation alone does not capture that source behavior. With ideal zero-impedance sources, the defined stage increments remain fixed while the extra capacitances change source currents.
Unequal voltage sharing appears through the actual impedance and control relationships, or through a different topology, not merely because capacitances exist. Solve the coupled nodal circuit with those relationships. Then report each stage’s voltage increment and each platform’s absolute potential.
A capacitance matrix from electrostatic modeling should use the same conductor definitions as the circuit. Merging two physically distinct structures in the field model can remove the very interstage branch being investigated.
Check geometry changes as electrical changes
Platform position, nearby grounded structures and electrode geometry can alter capacitances. Compare supported layout cases rather than importing one capacitance set into every laboratory arrangement.
Assess sensitivity to uncertain capacitances and stage impedances. If small changes produce a large voltage redistribution, the model needs sufficient geometric and measurement support before the result is used for insulation evaluation.
Retain the local voltage distribution with the geometry and source model that produced it. Use the governing stage-to-stage potential difference in the interstage insulation check.
Solve the driven nodes before assigning stage voltages
Apply complex branch currents and Kirchhoff balance [2] with both active stage sources retained. The second-stage source floats on node 1; its current contributes to the first-stage series drop as well as its own.
Assume two in-phase 100 kV sources, each with j10 kΩ series impedance at 50 Hz, and shunt capacitances of 10 nF from node 1 to ground and 1 nF from node 2 to ground. Nodal solution gives V₁ = 103.907 kV and V₂ = 204.550 kV. Stage increments are therefore 103.907 and 100.643 kV. Assign those actual potentials to the insulation model rather than dividing the 204.550 kV total equally.
References
- HIGHVOLT Prüftechnik Dresden GmbH, HVAC Test Systems Based on Transformers, 1.10/5 WP, November 2020.
- U.S. Department of Energy, DOE-HDBK-1011/3-92, Electrical Science, Volume 3, June 1992.