OLTC Transition-Resistor Energy: Integrate Each Actual Branch Current

  • Chenfan Power

Integrate the current through each OLTC transition resistor over its actual conduction intervals. The switching state sets load transfer and circulating components, which together determine the resistor’s single-operation energy.

The relevant quantity is the time integral of resistor dissipation. A through-current rating, a step voltage and a nominal operation duration do not, by themselves, provide that integral.

Reconstruct the circuit states for the proposed design

A transition impedance supports load transfer while limiting circulating current; the current in each conducting resistor follows the switching arrangement. [2]

Start from the approved switching diagram for the actual OLTC and winding connection. Identify each interval in which a resistor conducts, the terminals that drive its current and the state of any bypass path. Retain the direction of the tap change where it alters the sequence.

A resistor branch may carry load-transfer current in one interval and circulating current in another. The transformer terminal current therefore cannot be substituted for every branch waveform. An operation counter also contains no information about those individual electrical intervals.

Integrate resistor dissipation with consistent definitions

For a real resistor represented by R(t), its single-operation energy is:

E_R = ∫ R(t) i_R(t)² dt

Use the actual branch current and the time interval containing its dissipation. A constant resistance is a declared approximation. Where temperature changes resistance appreciably, the relevant resistance history belongs in the calculation.

For a constant R over an interval Δt, define an interval-effective RMS current as the square root of the mean of i² over that interval. Then E = R I_eff² Δt. This effective RMS is tied to the selected interval, which may be shorter than a mains cycle. It is not automatically the steady-state RMS load current or a sinusoidal phasor.

Check the current and timing measurements together. Clipping, insufficient bandwidth or a missing interval can remove the very part of the waveform that contributes strongly through i². If only a model supplies the current, retain its circuit, initial conditions and applicable validation basis.

Separate load sharing from circulating current

For an illustrative symmetric two-resistor bridge, let both resistors have the same R and define currents into the common load node. With load current i_L and circulating component i_C, write:

i_A = i_L/2 + i_C; i_B = i_L/2 − i_C

The instantaneous branch currents sum to i_L. Their resistor powers sum to:

R(i_A² + i_B²) = R i_L²/2 + 2R i_C²

The individual cross terms cancel in this equal-resistance sum, although they affect the allocation between resistors. This decomposition belongs to the stated symmetric bridge. An unequal-resistance or differently connected OLTC needs its own current solution.

Do not add a separate circulating-energy estimate after integrating branch currents that already include that component. That would count its dissipation twice.

Work a transparent single-operation energy ledger

Assumption: Consider an assumed two-resistor model with R_A = R_B = 0.5 Ω. It has three resistor-conduction intervals: A alone for 10 ms, both branches for 20 ms, and B alone for 10 ms. These are assumed model intervals, not a manufacturer operating sequence or permitted switching time.

During the bridge, choose i_L = 100h(t) A and i_C = 110h(t) A, where h has unit effective RMS over the bridge interval. Thus i_A = 160h and i_B = −60h. The negative sign indicates the chosen branch’s reverse current direction; its energy remains positive.

Fictional intervalA effective RMSB effective RMSDurationA energyB energy
A-only path100 A0 A10 ms50 J0 J
Symmetric bridge160 A60 A20 ms256 J36 J
B-only path0 A100 A10 ms0 J50 J
Operation subtotal——40 ms306 J86 J

The combined resistor energy is 392 J. In the same assumed bridge with circulating current omitted, the two branches would carry 50h each and dissipate 50 J during the bridge. Adding the two outside intervals gives 150 J. The difference is 242 J, exactly the bridge’s 2R∫i_C²dt contribution.

This comparison demonstrates why load-only substitution can miss energy. It supplies no actual step voltage, physical branch waveform, OLTC rating or acceptable resistor temperature.

A fictional three-interval model lists two resistor branch currents and energies of 306 J and 86 J, with a 392 J operation subtotal and separate load-only comparison.
The original fictional interval ledger integrates the two branch currents separately. It distinguishes reverse current direction from positive heating and shows the circulating contribution without duplicating it.

Keep resistor energy separate from the complete switching duty

The calculated energy is heat produced in the represented resistors. It is not contact arc energy, mechanical work or the complete transient energy exchange. Those terms require their own applicable quantities and boundaries.

Likewise, a single-operation energy does not establish repeated-operation thermal capability. Resistor temperature, heat transfer and recovery between operations belong to a separate thermal assessment. No universal interval between tap changes follows from the example.

Keep transition resistance, step voltage and through-current consistent with the proposed configuration. A changed operating duty changes the branch-current and energy assessment.

Preserve the evidence behind the result

Retain the actual circuit states, resistor values or histories, branch-current traces, conduction intervals and the integration method. Reconcile the branch sum with the intended load-current reference and verify that every represented interval is included once.

Report energies for each resistor and the defined operation subtotal. Connect those results to the proposed manufacturer’s switching and thermal capability evidence under the same winding connection and duty.

Follow each conducting path through the operation and integrate load transfer and circulation together. Report the branch energies and connect them to the manufacturer’s switching and thermal evidence for the same duty.

IEC 60214-1 covers performance requirements and test methods for tap-changers and their motor drives. Use that framework for the equipment-specific acceptance evidence. [1]

References

[1] IEC, IEC 60214-1:2014, Tap-changers — Part 1: Performance requirements and test methods.

[2] Dieter Dohnal, Maschinenfabrik Reinhausen, On-Load Tap-Changers for Power Transformers, 2013.