Assess OLTC breaking duty from the actual contact current and recovery voltage. Track current zero against the prospective voltage and include the transition branch’s load-transfer and circulating components.
The assessment therefore needs two traces tied to one circuit state: the current being interrupted and the voltage that the opening contact must recover against. A load power-factor label is an input to that circuit assessment, rather than a complete contact-duty specification.
Identify the actual breaking contact
Start with the applicable OLTC switching arrangement, winding connection and tap-change direction. Distinguish a contact that interrupts current from one that carries current or selects a disconnected tap. Their electrical duties are different.
Dohnal relates vacuum switching to current-voltage phase and voltage recovery after current zero. Those quantities must refer to the actual breaking contact. [2]
Record whether the contact current contains load transfer, a circulating contribution or a capacitive component. A terminal load current that is in phase with its voltage can still produce a differently phased transition-branch current when the switching loop has its own impedance.
Distinguish load displacement factor from contact phasing
For sinusoidal voltage and current, displacement power factor is the cosine of their relative angle. With distorted waveforms, total power factor also depends on distortion; one scalar factor cannot reconstruct the harmonic current or its zero crossings.
Even in a sinusoidal case, the phase reference matters. A load angle measured against a transformer terminal voltage is not automatically the angle between contact current and the prospective voltage across that contact.
Calculate the phase mapping from the same circuit topology. Include step voltage, transition impedance, winding coupling and the relevant branch state. Coarse–fine loop leakage can change the phase between breaking current and recovery voltage. [2]
Use a restricted phase example to expose the difference
Assumption: Consider an idealized comparison at 50 Hz. Assume, specifically for this illustration, that the chosen contact current follows the sinusoidal load current and its prospective power-frequency background voltage is in phase with the load-voltage reference. This restricted mapping is not asserted for every OLTC.
Let the contact current be 100 A RMS in every case and define:
i(t) = √2 × 100 sin(ωt − δ) A
u_bg(t) = 100 sin(ωt) V
The background voltage has an assumed peak of 100 V. It is neither the network voltage nor a measured transient recovery voltage. The topology and amplitudes stay fixed; only the declared relative phase δ changes.
At the selected natural current zero, ωt = δ. The background-voltage magnitude there is 100|sinδ| V. The time from the background-voltage zero is δ/ω for the selected quarter-cycle example.
| Declared displacement factor cosδ | Relative angle δ | Time of selected current zero | Background voltage magnitude there |
|---|---|---|---|
| 1.0 | 0° | 0 ms | 0 V |
| 0.8 | 36.87° | 2.048 ms | 60.00 V |
| 0.5 | 60.00° | 3.333 ms | 86.60 V |
These calculated values show a phase effect with unchanged RMS current. They do not rank real tap-changer duties or establish a permitted power-factor range.

Restore the transient recovery calculation
The voltage across a conducting arc is not the unrestricted background waveform. After interruption, local inductance, capacitance, current transfer and the dielectric recovery of the contact region determine the actual recovery process.
The power-frequency background value at current zero is therefore only one part of the assessment. It supplies neither the transient rate of rise nor a restrike prediction. A zero background value in the unity-factor example does not prove that the actual contact recovery is harmless.
Retain the contact’s precise voltage terminals. A system phase-to-ground voltage, the voltage between adjacent taps and the voltage across the breaking contact are different quantities. Replacing one with another can create a plausible-looking but physically irrelevant recovery trace.
Compare like-for-like contact duties
For a phase sensitivity study, hold the OLTC topology, tap pair, current-reference direction, transition-resistor configuration and applicable excitation basis fixed. State any changed load impedance and recalculate the contact current if that change affects its branch sharing.
In a real bridge, keeping load RMS constant may not keep breaking-contact RMS constant. Both its magnitude and phase can change through the circulating component. Preserve the complete branch-current solution instead of forcing the illustrative direct-current mapping onto it.
Use the same definition of contact opening and current interruption across cases. Distinguish natural current zero from a different interruption mechanism. The first suitable zero after a mechanically defined opening event depends on the actual opening instant; the table supplies no operating timing instruction.
Retain evidence that supports the application decision
Keep the winding and switching diagrams, synchronized current and voltage definitions, model parameters and the manufacturer’s applicable switching-capability evidence. A reported phase angle is only meaningful when its two quantities and reference directions are identified.
Where measurements are used, preserve instrument bandwidth and timing alignment sufficient for the contact recovery of interest. Where a model is used, retain its initial conditions and the treatment of the arc and post-interruption circuit.
Trace load phase through the specified switching loop into the contact current and recovery process. Use that paired current-voltage duty with the applicable switching-capability evidence for equipment selection or acceptance.
IEC 60214-1 covers performance requirements and test methods for tap-changers and their motor drives. Use that framework for the equipment-specific acceptance evidence. [1]
References
[1] IEC, IEC 60214-1:2014, Tap-changers — Part 1: Performance requirements and test methods.
[2] Dieter Dohnal, Maschinenfabrik Reinhausen, On-Load Tap-Changers for Power Transformers, 2013.