Segmenting Wide Foil: Compare the Current Loops and the Added Connections

  • Chenfan Power

Compare foil segmentation through its complete circuit. Define the cuts, insulated surfaces and reconnection points, then calculate both the shortened local eddy paths and any circulating paths formed by the end connections.

The drawing must distinguish an isolated eddy-current benchmark from a working winding carrying terminal current. These are different boundary conditions. A reduction demonstrated under one does not automatically describe the other.

State what segmentation actually changes

A slit along the conductor’s length divides its width. Dividing its thickness into parallel layers is another change, and increasing the number of series turns is another. Each changes different field directions, current paths and connections. The term segmented foil alone does not identify the proposed design.

Record each strip’s width, thickness and route, including material removed by gaps. Identify whether the strips connect in series, in parallel at both ends, or through a specified transposition arrangement. Preserve the relevant insulation and end geometry in the model.

For parallel strips, the end buses and intermediate connections are part of the winding. A longitudinal insulating gap prevents current crossing the gap locally. It does not prevent current traveling down one strip, through an end connection, and back through another.

Use an isolated-strip benchmark within its assumptions

Derive the isolated-strip comparison from Faraday’s law and Joule heating. State the field orientation, zero additional net current and current-return boundary before applying a width scaling.

An, separately stated width benchmark can be derived from the same field laws. Consider a long uniform strip of length L, width w and thickness t. Let an imposed sinusoidal magnetic flux density B_RMS be normal to the broad face. Neglect electromagnetic reaction and the end-return regions, and consider only the longitudinal induced-current component in the interior.

With x measured across the width from its center, Faraday’s law gives an electric field proportional to x. Requiring the additional longitudinal current to integrate to zero sets its constant term. For ordinary real conductivity σ, the resulting benchmark is:

P_strip = σ ω² B_RMS² L t w³ / 12

Here ω is angular frequency and the amplitude is RMS. The expression is the integral of the squared interior current density divided by conductivity. It excludes transport current, connections, altered field penetration and end losses.

Now divide the same ideal total width into n equal electrically isolated strips. Ignore the width removed by insulating gaps and impose zero additional net current on each strip. Adding their benchmark losses gives:

P_n / P_1 = 1 / n²

Two ideal isolated strips give one quarter of the benchmark term. Four give one sixteenth. This is a conditional geometric result, not a predicted percentage reduction in a complete winding.

A conceptual diagram compares unsplit foil, isolated strips, parallel end-connected strips and series strips, with conditional normalized loss and a fictional joint budget.
The original topology comparison separates a frozen-field isolated-strip benchmark from connected winding paths. The normalized values apply only to the stated benchmark; the connected strips require their own current solution.

Restore the connections before estimating winding loss

Joining the strips at both ends removes the independent zero-additional-current condition used in the benchmark. Each branch can carry a nonzero additional current while their sum is zero. The induced voltage around the loop between branches depends on the flux linked by their complete routes.

For a working winding, calculate branch currents using the applicable circuit and field representation. Include terminal impedances, mutual coupling and unequal linked flux where relevant. The field also responds to the resulting currents, so retaining a frozen input field needs an explicit justification.

A series connection has a different circuit constraint. It does not create the same parallel branch sharing, but its bridges, routing and number of turns must be included in the comparison. Neither topology can be selected solely from the isolated-strip ratio.

Avoid adding a separately calculated circulating-loss term to a field solution that already contains those currents. Define the included current components and physical integration regions so the same dissipation is counted once.

Put additional joint losses in the same ledger

Connections have both electrical and manufacturing consequences. A comparison should preserve the current through each joint, its represented resistance, temperature basis and uncertainty. A joint’s location may also change leakage-field exposure and local cooling access.

Assumption: Consider an illustrative budget rather than a claimed design result. Suppose a candidate’s appropriately scoped model shows 60 W less in one eddy-loss term. Suppose it also adds two series joints, each carrying 500 A RMS, with an assumed resistance of 20 micro-ohms per joint. Their represented dissipation is:

P_added joints = 2 × 500² × 0.000020 = 10 W

The remaining margin is 50 W before other changed losses. These deliberately assumed values do not prove that a segmented winding saves 50 W. The winding-current redistribution, end-region losses and any further affected domains still need to be evaluated.

If the connections actually carry different branch currents, calculate each joint with its own current. Do not apply total terminal current to every parallel joint or divide current evenly merely because the strips look similar.

Compare manufacturable candidates under the same duty

A useful study retains the reference and candidate conductor volumes, turn count, temperature basis, excitation and accepted thermal conditions. If the candidate removes metal, changes mean route length or alters cooling channels, those changes belong in the comparison rather than being hidden behind a segmentation label.

Check whether the proposed insulation between strips remains effective through assembly and operation. An unintended bridge changes the very topology that the electromagnetic result assumes. This requires design and production evidence, rather than a generic instruction to cut an existing winding.

Report local eddy loss, connection loss and other changed losses separately, then combine them over a justified boundary. Preserve local heat-source information because a favorable power integral does not establish an acceptable joint or conductor temperature.

Select the segmentation from the actual loops, branch currents and connection losses. Carry those heat sources into the thermal assessment so the width change delivers a useful result in the working winding.

The transformer loss boundary includes winding resistance heating. [1] For a measured comparison, retain the uncertainty and any shared error contributions with the reported difference. [2]