  • Chenfan Power

Solve unequal end-turn current sharing with the complete complex branch impedances and route-linked voltages. A longer end adds resistance at the same material, area and temperature; its AC current also depends on reactance and electromagnetic coupling.

A meaningful loss comparison separates the straight winding section from the end region, retains current phase, and identifies which electromagnetic coupling is included. Averaging the conductor lengths discards the information needed to calculate unequal sharing.

Draw complete branches between common terminals

Start at one common electrical terminal and trace each branch to the other. Include straight conductor sections, bends, end connections, joints and lead transitions. A branch ends at the common node defined by the circuit, rather than at the end of the visible coil body.

Record material, cross-section and the temperature used for resistance. For a uniform segment, R = ρl/A is a useful DC representation. Sum it over the actual segments. A longer route increases that represented resistance only when resistivity and area remain comparable; a larger area can change the conclusion.

End-region reactance is not a resistance calculated with another coefficient. Route geometry and linked flux matter. Preserve the self and mutual terms, or explain the reduction that replaces them with effective branch impedances. Unequal induced contributions also belong in the equations.

Keep the impedance representation explicit

For a limited two-branch example, assume the network has already been reduced to Z₁ and Z₂ under a common sinusoidal drive U. Let any separately represented unequal induced source be absent, and let no off-diagonal coupling remain in this reduced representation. Use RMS phasors.

The current division is then:

I₁ = I_total Z₂ / (Z₁ + Z₂)

I₂ = I_total Z₁ / (Z₁ + Z₂)

Both branches satisfy the same reduced voltage U = Z₁I₁ = Z₂I₂. This scalar division is not a substitute for solving a general coupled winding network. If mutual impedances or unequal induced sources remain, restore them before using the result.

The branch equations below follow directly from equal terminal voltage and current continuity. If unequal induced voltages or off-diagonal mutual terms remain, include them before solving current sharing.

Work a case where the longer branch carries more current

Assumption: Assumption for the reduced circuit at 50 Hz: the straight-section resistance is 0.8 mΩ in both branches. The shorter end contributes 0.2 mΩ and the longer end 0.5 mΩ. Assign total effective reactances of 3.0 mΩ and 1.8 mΩ respectively. Hold the material state and temperature fixed.

The reactances are independent assumed circuit inputs. No measured geometry or inductance calculation supplies them, and their difference is not claimed to follow automatically from a particular bend length.

Reduced branchStraight REnd RTotal ZCurrent at I_total = 1,000 + j0 A RMS
Shorter end0.8 mΩ0.2 mΩ1.0 + j3.0 mΩ410.52 − j74.13 A
Longer end0.8 mΩ0.5 mΩ1.3 + j1.8 mΩ589.48 + j74.13 A

The impedance magnitudes are approximately 3.162 mΩ and 2.220 mΩ. Despite its higher resistance, the longer-end branch has the smaller impedance magnitude in this declared example. It therefore carries the larger current magnitude: approximately 594.12 A instead of 417.16 A.

Relative to the total-current reference, the shorter-end current has phase −10.24° and the longer-end current +7.17°. Adding the complex currents gives the prescribed total. Adding their magnitudes does not reproduce that total because the currents are not in phase.

A fictional two-branch winding circuit separates straight and end resistance and tabulates complex currents, phases and resistor losses for unequal end routes.
The original reduced-network example separates straight and end resistance and shows current phase. The longer-end branch carries more current because its assigned effective reactance makes its impedance magnitude smaller; the drawing is not an actual winding geometry.

Calculate losses with each branch’s own RMS current

Using the represented real resistances, the branch resistor losses are R₁|I₁|² and R₂|I₂|². They are approximately 174.02 W and 458.88 W. The sum is 632.90 W.

The end-region portions alone are approximately 34.80 W and 176.49 W, from their respective 0.2 mΩ and 0.5 mΩ resistances. The corresponding straight portions are approximately 139.22 W and 282.39 W. These parts sum back to the two branch totals.

This is a resistor-loss ledger within the illustrative reduced network. It includes neither a spatial eddy-current solution nor an independently measured hotspot. If an effective AC resistance already contains a modeled eddy-loss term, do not add that same term again under an end-loss heading.

The common voltage calculated from either branch is approximately 0.63290 + j1.15743 V. The real part of U multiplied by the conjugate total current gives the same 632.90 W, providing a separate circuit consistency check.

Identify the conditions behind the reversal

Under a common drive, a longer branch can carry more current when its complete impedance magnitude is smaller. This can occur in a reduced model despite a higher resistance, as the example demonstrates. Geometry, conductor area, electromagnetic coupling and linked flux determine whether that condition exists in a real winding.

Unequal induced sources create another mechanism and require a different circuit solution. They must not be concealed by reporting only conductor resistance or by calling every current difference a length effect.

For a fixed branch-current comparison, the added resistance of a longer end can be calculated directly. For a current-sharing comparison, the branch currents themselves change. State which comparison is being made before discussing additional watts.

Retain evidence that resolves the end region

The final assessment should preserve branch routes, resistance measurements or calculations, operating temperature, frequency, current reference and the complete impedance model. Show that the represented terminals match the actual connection boundaries.

Where three-dimensional end fields control the difference, retain the applicable field representation rather than infer them from a two-dimensional straight section. Relate the loss distribution to cooling and temperature assessment before accepting a conductor or joint thermal result.

Solve the actual branches with their phase and coupling basis, then reconcile regional losses with circuit power. Use end length as a geometric input alongside the impedance evidence that determines current sharing.

The transformer loss boundary includes winding resistance heating. [1] For a measured comparison, retain the uncertainty and any shared error contributions with the reported difference. [2]

References

[1] U.S. Bureau of Reclamation, Transformers: Basics, Maintenance, and Diagnostics, April 2005, Sections 2.6 and 2.9.

[2] Barry N. Taylor and Chris E. Kuyatt, NIST Technical Note 1297, Guidelines for Evaluating and Expressing the Uncertainty of NIST Measurement Results, 1994.