Track the winding response beyond the electromagnetic force peak. Inertia carries motion forward, and kinetic energy can continue converting into strain energy after the pulse ends. Use the complete motion history to locate the controlling displacement and support demand.
The useful comparison is between force duration and the participating structural periods. A short, intense pulse and a sustained force with the same maximum can generate very different displacements and support reactions.
Keep current, force and motion on one time axis
When the electromagnetic field distribution scales with current in a linear magnetic approximation, an electromagnetic force component may scale with current squared. That relationship gives the excitation history only for that specified field pattern. Mechanical response still follows the mass, stiffness, damping and contact conditions.
For one structural coordinate x, the linear equation is:
m ẍ + c ẋ + kx = F(t).
For this linear oscillator, displacement follows the convolution of force history with the structural impulse response. It therefore retains inertia and phase relative to the applied force.
In a multi-mode model, the electromagnetic load must also be projected onto each mode. A large force at one location can have weak participation in a particular mode. Two modes can combine constructively at a spacer and cancel at a distant measurement point. Compare local motion and contact force, not only a single global displacement norm.
A rectangular pulse makes the timing difference explicit
Assumption: Take an initially stationary, undamped linear oscillator with m = 10 kg, k = 1 MN/m and an applied force of 1,000 N lasting T = 5 ms. Its natural angular frequency is 316.228 rad/s and its natural frequency is 50.329 Hz. The static deflection under a sustained 1,000 N load is 1 mm.
During the pulse:
x(t) = (F₀/k)[1 − cos(ω_n t)].
After the pulse ends:
x(t) = (2F₀/k) sin(ω_nT/2) sin[ω_n(t − T/2)].
Because this pulse is shorter than half the natural period, the first positive displacement maximum occurs at:
t_peak = T/2 + π/(2ω_n).
The result is 1.422 mm at 7.467 ms. At that instant, the applied force is zero. At 5 ms, when the pulse ends, the displacement is only 1.010 mm and the mass is still moving outward.
This is an idealized pulse calculation. It isolates the timing mechanism without contact switching or damping; it does not represent a measured transformer current waveform.

Static amplification depends on duration
For the same ideal oscillator and a pulse shorter than half a period, the ratio of maximum displacement to static deflection is 2 sin(ω_nT/2). A sufficiently short pulse gives little time to build displacement, even when its peak force is high. A step load maintained through half a period reaches twice the static deflection in this undamped model.
Determine dynamic amplification from force duration, initial state and natural period. With damping, the peaks and phase change. With unilateral contact, stiffness can change during the event and reimpact may govern a local support load. Those mechanisms must be included when they are active in the assembled winding.
Review the force-motion relationship where damage could begin
Extract the current history, electromagnetic force, displacement, velocity and support reaction with consistent timestamps. Plot them at the relevant conductor span, end block or press ring. Record both the force at maximum displacement and the displacement at maximum force. Their difference reveals whether a static approximation is physically representative.
Then check the dynamic energy balance. During the rising response, input work is divided between kinetic and strain energy. After the external pulse ends, the continuing movement converts kinetic energy into strain energy. Numerical damping that removes this energy too quickly can reduce the calculated peak without improving the actual structure.
Compare maximum relative movement, minimum contact pressure, peak support reaction and retained deformation over the complete response. Locate each controlling instant in the calculated or measured history and relate it to the excitation timing.
IEC 60076-5 addresses thermal and dynamic withstand of external short circuits. The support model and its validation should resolve the mechanical quantity used in that assessment. [1]
Carry uncertainty in the measured model inputs and responses into the comparison, including correlated contributions. [2]
References
[1] IEC, IEC 60076-5:2006, Power transformers — Part 5: Ability to withstand short circuit.
[2] Barry N. Taylor and Chris E. Kuyatt, NIST Technical Note 1297, Guidelines for Evaluating and Expressing the Uncertainty of NIST Measurement Results, 1994.