Build disc-winding loop inductance from the forward path, return path and their mutual interactions. Keep each partial coefficient tied to its conductor partition and reference orientation before transforming the branch currents into the intended loop.
Calculation basis. Unless a value is explicitly attributed to a cited source, numerical inputs in the demonstrations are assumptions for the stated model. Normalized variables are dimensionless. The examples define their own geometry, excitation and measurement boundary.
For a disc-winding model, first preserve that connectivity. Then transform the branch representation into the intended loop or port variables. A plausible diagonal coefficient cannot compensate for an omitted lead, return winding or closure path.
Separate a conductor coefficient from a complete circuit
Ruehli’s original partial-inductance paper divides closed conductor loops into segments and reconstructs loop inductances by signed sums of their interactions. Its sign rule depends on assigned current directions; its discussion of open loops explicitly distinguishes a removed closing path from a fully specified closure. [1]
Represent forward and return conductors either as separate oriented paths or as one closed loop, and label which extraction is supplied. Preserve the same closure in the circuit transformation.
These sources concern interconnect structures. They support the partition, return-path and orientation principles, not validated transformer disc-winding values or a generic approximation for a nonlinear magnetic core.
Declare what the extraction represents
List disc sections, turn connections, inter-disc leads, terminals and the conductor route that closes the studied current. Specify which paths carry independently imposed currents and which currents are constrained by their connections.
State whether current is uniform, filament-resolved or computed from a frequency-dependent field solution. Refine the cross-section where skin and proximity effects matter; one low-frequency coefficient does not establish a broadband response.
Material assumptions also belong in this record. A nonmagnetic quasistatic conductor extraction excludes nonlinear core magnetization and may exclude conducting structural responses. It cannot be labeled the transformer’s total inductance or percent impedance without a separate model definition and evidence.
Transform currents and energy together
For the original algebraic illustration here, define a real, reciprocal, fixed inductance representation with oriented branch-current vector i, signed partial matrix L_p and magnetic energy W = ½ iᵀ L_p i.
Introduce independent loop-current vector I and a signed connectivity matrix T such that i = T I. Substitution gives:
L_loop = Tᵀ L_p T, and W = ½ Iᵀ L_loop I.
T records both membership and direction. It is not obtained by retaining an arbitrary subset of diagonal entries. Ruehli separates geometric magnitudes and sign factors in his notation; this article instead incorporates the orientation signs in L_p and uses signed T consistently. Do not apply both sign treatments a second time.
The transformation assumes the declared current constraints and linear energy representation. Capacitive branch currents, eddy-current paths and distributed terminal behavior may require additional unknowns or a frequency-dependent network rather than one fixed series-loop current.
Audit an assumed forward-and-return pair
Consider two effective path groups, including the represented closure contributions. Choose the assumed matrix, in µH:
L_p = [[2.0, 1.2], [1.2, 3.0]].
Both reference arrows point in the same geometric direction. A circulating current therefore has i_f = I and i_r = −I, giving T = [1, −1]ᵀ. Its loop inductance is:
L_loop = 2.0 + 3.0 − 2 × 1.2 = 2.6 µH.
At an instantaneous I = 100 A, energy is ½ × 2.6 × 10⁻⁶ × 100² = 0.013 J, or 13 mJ. The current and coefficients are selected only for an algebraic audit; they are not product measurements or operating limits.
Keeping only the forward coefficient gives 2.0 µH and 10 mJ. It understates this assumed loop energy by 23.08%. The percentage measures the return-path omission for this matrix. A different geometry changes both self and mutual terms.
Reverse an arrow without changing the physics
Reverse the reference orientation of the return path. With S = diag(1, −1), the coordinates become i’ = S i, the matrix becomes L_p’ = S L_p S, and T’ = S T.
The off-diagonal entries are now −1.2 µH, while T’ = [1, 1]ᵀ. The transformed loop inductance remains 2.6 µH. Its energy remains 13 mJ at the same physical current.
| Representation of the same assumed loop | Cross coefficient | Return coordinate | Loop result |
|---|---|---|---|
| Both reference arrows parallel | +1.2 µH | −I | 2.6 µH |
| Return reference arrow reversed | −1.2 µH | +I | 2.6 µH |
| Return path discarded | Not retained | Not represented | 2.0 µH, incomplete |
A sign flip in the coefficient without the corresponding current-coordinate change alters the model. Consistent orientation transformations leave the physical energy and port behavior unchanged.

Test definiteness on the intended current space
For this real reciprocal energy model, nonnegative energy is required for every physically admissible current. If its branch coordinates are independently admissible, L_p must be positive semidefinite. If connectivity restricts them, inspect Tᵀ L_p T on the independent current space as well.
Positive diagonal entries alone are insufficient. The assumed two-path matrix has leading diagonal 2 µH, determinant 4.56 µH² and eigenvalues 1.2 and 3.8 µH, so it is positive definite. Congruence through T preserves nonnegative loop energy. Strict positive definiteness of every reduced matrix is not universal when redundant current coordinates or zero-energy modes remain.
As a deliberate defective example, increase the mutual entry to 3.0 µH while retaining diagonals 2.0 and 3.0. The determinant becomes −3 µH², and the same circulating current gives L_loop = −1 µH and energy −5 mJ at 100 A. This violates the declared storage model. The constructed matrix error is detectable directly from storage positivity.
Keep the returned matrix reproducible
Deliver the conductor partition, path orientations, node connections, current transformation, units, material and frequency assumptions with the extracted coefficients. Check symmetry and energy without concealing raw extraction errors behind a correction.
Refine the conductor and return-path representation while comparing the same loop or port observable. Report any omitted closure contribution and the evidence supporting its omission. A return plane, another winding and a remote lead are different geometries, even when each is casually called ground or return.
Deliver the matrix with its current circuit, return geometry and sign transformation intact. Validate the chosen loop or port observable over the winding’s supported band so the coefficients remain traceable to the extraction they represent.
Ruehli reconstructs closed-loop inductance from signed interactions between conductor segments. Retain the complete return path and current orientation before using a coefficient in the winding circuit. [1]
Gustavsen and Heitz show that fitted multiport accuracy depends on terminal conditions and the visibility of small modes. Validate the response used for the engineering decision under its actual terminal loads. [2]
References
[1] A. E. Ruehli, Inductance Calculations in a Complex Integrated Circuit Environment, 1972, DOI:10.1147/rd.165.0470.
[2] B. Gustavsen and C. Heitz, Modal Vector Fitting: A Tool for Generating Rational Models of High Accuracy with Arbitrary Terminal Conditions, 2008, DOI:10.1109/TADVP.2008.927810.