Heat-Balance Checks for Transformer Temperature-Rise Results

  • Chenfan Power

Close a heat balance across one defined transformer boundary. A gap between losses and cooler transfer may include surface rejection, stored heat or measurement error [1]. Allocate those independently before diagnosing the residual.

A heat balance is a useful consistency check when its inputs are independently measured or estimated. It becomes circular if an unknown storage term is chosen solely to make the totals agree.

Heat-Balance Checks for Transformer Temperature-Rise Results: technical review table
Use flow and temperature measurements at the same interface

Draw one boundary for all the terms

For a selected equipment boundary, write Ptransformer + Pauxiliary, inside = Qcooler + Qother surfaces + dU/dt. Include only auxiliary heat that enters that boundary. Account for separate cooling circuits and identify any heat transfer that the measurements omit.

A pump motor can introduce heat into the oil circuit. A fan motor may release much of its heat outside the chosen oil-system boundary. Their electrical input powers should not both be added automatically to the same balance. The physical arrangement determines the allocation.

Use flow and temperature measurements at the same interface

For a cooler oil stream with appropriate property data, Q ≈ ṁcp(Tin − Tout). With illustrative inputs2kg/s,2kJ/(kg·K) and8K, the calculated transfer is32kW. These are chosen example values, not specified oil properties or cooler ratings.

Illustrative energy balance with independently assigned terms
TermPowerBasis to establish in a real test
Transformer heat input40 kWMeasured losses representative of the test condition
Auxiliary heat entering the boundary1 kWActual pump or auxiliary heat allocation
Oil-side cooler transfer32 kWFlow, property data and matched inlet/outlet temperatures
Other boundary heat rejection5 kWIndependent estimate of tank and other surface transfer
Transient stored energy rate4 kWIndependent temperature-rate and heat-capacity estimate

The input is41kW and the three outgoing or storage terms also total41kW. The example includes continuing thermal storage. It therefore demonstrates energy consistency, not thermal steady state.

For this boundary, the independently assigned 4 kW storage term must come from supported heat capacity and temperature-rate data [1]. A thermal-test method [2] and its qualifying interval still determine whether a steady result has been obtained; zero algebraic residual alone does not.

Separate energy consistency from steady operation

The assumed cooler stream removes 2×2×8 = 32 kW. Inputs total 40+1 = 41 kW and removal/storage terms total 32+5+4 = 41 kW. The zero residual is consistent, while the independently assigned 4 kW storage term means the equipment remains transient. Qualify thermal stability separately.

Investigate a residual before declaring the test wrong

Check flowmeter location, bypass paths, fluid properties and temperature-channel alignment. A small inlet/outlet difference can make the calculated transfer sensitive to differential probe errors. Shared calibration effects may correlate, so the uncertainty of a difference is not always the sum of two independent temperature uncertainties.

References

  1. U.S. Department of Energy, DOE-HDBK-1012/2-92, Thermodynamics, Heat Transfer, and Fluid Flow, Volume 2, 1992.
  2. IEC, IEC 60076-2:2011, Power transformers — Part 2: Temperature rise for liquid-immersed transformers.