Transformer Hot-Spot and Resistance Temperatures: Why They Differ

  • Chenfan Power

Compare local and resistance-derived temperatures by their spatial and time definitions. A sensor at 120 °C and a resistance result of 100 °C can describe the same winding when a local hotter section sits above the conductor-path average. [1]

The first investigation is therefore a comparison of measurement definitions and times. Treating the readings as competing measurements of one identical temperature can send the investigation towards a calibration fault that does not exist.

Transformer Hot-Spot and Resistance Temperatures: Why They Differ: technical review table
Understand the averaging implicit in resistance

Understand the averaging implicit in resistance

For one conductor material with an approximately linear resistance-temperature relation, the total resistance is the sum of its local contributions. The resulting converted temperature is weighted by each section’s reference resistance. For uniform material and cross-section this becomes a length-weighted conductor average under the stated assumptions.

In an illustrative two-section winding, suppose the sections have equal reference resistance and temperatures of80°C and120°C. The resistance-derived temperature is100°C, while a correctly positioned local sensor can read120°C. The20K difference describes the chosen thermal distribution; it is not evidence that either instrument is wrong.

Interpret the mismatch through the measured quantities
ObservationPossible physical explanationComparison needed
Local reading exceeds the resistance temperatureSensor samples a hotter conductor region than the resistance-weighted meanSensor placement and the predicted spatial temperature distribution
Selected local reading is lower than the resistance temperatureThe probe may sample a cooler region, another material or a poorly coupled positionInstallation details and other temperature channels
Difference changes with cooling configurationOil-flow redistribution can change the local-to-average relationMatched load, cooling state and actual channel locations
Difference appears only after shutdownSensor and resistance estimate may refer to different times or recovery modelsAligned acquisition times and resistance extrapolation record

Check sensor position against the possible hot-spot locations

A fixed sensor measures its installation point. The hottest conductor location can differ from the predicted location or move when load partition, tap position or cooling changes. A low reading at one installed probe does not establish that the entire winding maximum is low.

Review sensor attachment, depth, thermal contact and channel identity. A probe installed in insulation or adjacent oil may measure a different thermal response from the conductor itself. These installation effects should be distinguished from a real conductor gradient.

A spatial thermal field can contain a local maximum above its weighted mean [2]. A stable difference between a probe and resistance temperature is therefore not a calibration correction until location, weighting and time have been reconciled.

Keep the resistance-weighted mean distinct

For the assumed two equal-reference-resistance sections at 80 and 120 °C, the converted mean is 100 °C and the local-to-average difference is 20 K. If the hotter section instead carries an assumed 75% reference-resistance weight, the mean becomes 110 °C. Use the actual conductor weighting and local probe position before calling their difference instrument error.

Resolve timing before applying an error allowance

A local sensor can provide a reading while heating is still applied. Resistance temperature may be reconstructed after shutdown. Compare the quantities at a consistent reference time and retain the extrapolation model and its sensitivity. Otherwise the subtraction includes both spatial and temporal differences.

References

  1. U.S. Bureau of Reclamation, FIST Volume 3-31, Transformer Diagnostics, June 2003.
  2. U.S. Department of Energy, DOE-HDBK-1012/2-92, Thermodynamics, Heat Transfer, and Fluid Flow, Volume 2, 1992.