Assess thermal equivalence using spatial losses and heat paths, not only total kilowatts. Moving heat among core, windings and structures can change component temperatures in the same thermal network [1].
This matters when comparing alternative heat-run arrangements, interpreting a revised design or judging whether an earlier test still represents a new loading condition. The useful question is whether the heat sources and their cooling paths remain representative of the quantity being assessed.

Keep the loss map alongside the total
Separate winding conductor loss, additional winding loss, core loss and heat generated in leads, clamps or shields. These sources occupy different positions. A watt generated near a poorly supplied winding duct has a different route to the cooling medium from a watt generated in an exposed structural surface.
The differences extend beyond distance. Oil velocity, duct restrictions, solid insulation, local contact and radiator operation affect the thermal response. Two designs with the same total loss may therefore have different winding averages, local hot spots and top-oil temperatures. Agreement at one sensor does not establish agreement at the others.
A small model shows the missing information
Consider an illustrative steady, linear two-node model. Its temperature rises satisfy ΔTc = 3Pc + Pw and ΔTw = Pc + 5Pw, with powers in kW and coefficients in K/kW. The subscripts identify core and winding nodes. The cross terms represent thermal coupling. These chosen coefficients demonstrate the calculation; they are not material properties or predictions for a product.
| Case | Core / winding heat | Total | Core rise | Winding rise |
|---|---|---|---|---|
| A | 8 / 2 kW | 10 kW | 26 K | 18 K |
| B | 2 / 8 kW | 10 kW | 14 K | 42 K |
Changing the heat split leaves the total unchanged but raises the winding node by 24 K. A real transformer needs a richer model, especially where oil-flow redistribution or temperature-dependent losses are important. The example establishes why total-loss equality alone cannot identify the temperature distribution.
Use the coupled-node result to challenge the proposed loss distribution [1]. The governing temperature-rise method [2] still defines the qualification quantity; numerical equality of total input does not establish equal component duty.
Use the two-node result in the equivalence decision
For the stated assumed coefficient matrix, the 8/2 kW core/winding split gives 26/18 K rises; the 2/8 kW split gives 14/42 K. Total remains 10 kW, while winding rise increases 24 K. Verify the component loss map and local cooling before extending a heat run based solely on total watts.
Compare the trial at the component being qualified
For each proposed equivalent test, list the service heat source, the source created during the trial and the measured response. Check whether frequency, flux, current distribution and cooling state change that comparison. A test that represents average winding heating may leave local stray-loss heating insufficiently represented.
References
- U.S. Department of Energy, DOE-HDBK-1012/2-92, Thermodynamics, Heat Transfer, and Fluid Flow, Volume 2, 1992.
- IEC, IEC 60076-2:2011, Power transformers — Part 2: Temperature rise for liquid-immersed transformers.