Test terminal-failure explanations against their physical paths: resistive contact heating, insulation breakdown and external conductor loading. Each can leave a melted terminal, so identify the observation that separates them before assigning a cause. [1]

Define mechanisms narrowly enough to test
For a contact-heating hypothesis, identify the proposed resistive interface and the current that could heat it. For an electrical-stress hypothesis, identify the insulation path and relevant operating or transient state. For an external-load hypothesis, identify the conductor restraint and force path into the terminal.
These are illustrative alternatives, not a complete catalogue. Construction and event records may suggest others, including a combination in which mechanical displacement changes electrical contact before arcing.
Use an elimination matrix
| Hypothesis | Expected evidence to seek | Evidence that would weaken it |
|---|---|---|
| Pre-existing contact heating | Protected interface alteration and comparable earlier resistance or thermal observations | Supported chronology placing interface damage after a separate fault |
| Insulation breakdown near the terminal | Consistent electrical path, preserved insulation features and event stress | Geometry or circuit state preventing the proposed path |
| External mechanical loading | Compatible restraint, displacement and paired contact or fracture marks | A load path inconsistent with the observed movement |
For every cell, distinguish absent evidence from evidence of absence. A missing earlier thermal image cannot refute heating. A properly documented measurement sensitive to the proposed heating could constrain it.
Seek contradictions before adding support
If one explanation requires terminal movement before a recorded fault stage, ask whether the aligned timeline establishes that order. If it requires current through an open path, verify the actual switching and connection state rather than assuming the path existed.
Do not double-count one observation. A melted surface, a rounded edge and a photograph caption saying overheated may all describe the same feature. They are not three independent proofs.
NASA distinguishes failure mode from physical mechanism [2]. For this terminal, melting is an observation to explain; the contact, insulation or mechanical sequence needs its own surviving evidence. Several descriptions of the same melted surface do not supply independent causes.
Calculate whether the contact-heating hypothesis has power
Assume a candidate joint carried 500 A RMS and had 0.20 mΩ resistance at the stated pre-fault temperature. Its I²R input would be 50 W; at 2.0 mΩ it would be 500 W. Seek preserved interface and historical evidence that discriminate those assumed states before assigning the melted terminal to pre-existing contact resistance.
Keep facts and interpretation in different columns
Retain measured values, photographs and source records separately from conclusions such as loose joint or overvoltage. Diagnostic electrical comparisons require consistent temperature, connection and tap boundaries; a changed test setup can imitate a component change.
References
- U.S. Bureau of Reclamation, FIST Volume 3-31, Transformer Diagnostics, June 2003.
- L. Ochs, NASA Goddard Space Flight Center, Basics of Failure Analysis, NASA Parts 101, December 4, 2024.