GIC pulse duration controls how much heat accumulates in transformer structures. Tie plates and clamps respond to local loss history, thermal mass and cooling, so equal current peaks can produce different hot-spot temperatures. [1] [2]
The NERC thermal assessment framework therefore distinguishes design-specific thermal responses and the duration of the applied current. Its example screening quantities are not universal transformer capability limits.

Hold the starting condition fixed
To isolate pulse width, retain the same initial loading, bulk-oil temperature, cooling configuration, AC voltage and current allocation through the windings. Different initial oil temperatures shift the absolute structural temperature even if the incremental rise is identical.
Keep the electromagnetic calculation separate from the thermal calculation. A DC current waveform produces a time-varying magnetic state and local loss input. That input then drives thermal nodes. The mapping from current to loss may be nonlinear; squaring a GIC trace without a justified electromagnetic relationship is not a substitute for it.
Build a duration envelope for each location
A simplified local node illustrates the distinction. Let its additional heating power be constant during a pulse, its thermal resistance be Rth and its time constant be τ. Starting at the unchanged baseline, the incremental temperature rise is Δθ(t) = Padd Rth[1 − exp(−t/τ)]. After the pulse, this isolated node’s increment decays exponentially if its surroundings remain at the baseline.
For an illustrative node with Padd Rth = 80 K and τ = 150 s, the following envelope results. These assumed values describe the calculation only.
| Pulse duration | Increment at pulse end | Interpretation |
|---|---|---|
| 30 s | 14.5 K | Limited time to approach equilibrium |
| 180 s | 55.9 K | Much greater stored heat at the same loss level |
| Repeated pulses | Calculate from the previous temperature | Cooling between pulses changes the next peak |
For variable loss input, integrate the node equation through the entire event rather than restarting every pulse from zero. Preserve pre-event heating and the cooling intervals. A longer pulse at a lower loss level can then be compared with a shorter, more intense pulse on temperature rather than current ranking.
Look beyond the end of the current pulse
A real structural assembly has several coupled thermal nodes. A sensor farther from the loss concentration can continue warming after GIC has fallen because heat is still arriving from the hotter region. The hottest location can also change as heat spreads.
Plot temperature envelopes for the credible governing parts, not one average core curve. Include the absolute starting temperature and the time at which each local maximum occurs. A loss model and a thermal model validated only in steady state may still need transient evidence before predicting a short pulse.
Rank events by local temperature histories and the applicable equipment limits. Keep peak current, pulse width, repeated exposure and cooling history together so the comparison captures the duty that governs structural heating.
References
- NERC, Transformer Thermal Impact Assessment White Paper, Project 2013-03 Geomagnetic Disturbance Mitigation, October 2017.
- U.S. Department of Energy, DOE-HDBK-1012/2-92, Thermodynamics, Heat Transfer, and Fluid Flow, Volume 2, 1992.