Grounding and auxiliary power excite a combined transformer’s windings differently. Keep auxiliary ratio, load-temperature performance and grounding-port impedance tied to their own test conditions, then assess the section currents where the two duties interact. [1]
Calculation basis. Project-specific values and gates in the illustrative screens below are assumptions; cited catalogue values retain their source test conditions.
Build the evidence map from the two functions and then add the simultaneous state. This avoids turning a familiar factory test label into an assumption that every operating duty has been covered.

Give each function its own test boundary
| Evidence family | What it can establish | What remains separate |
|---|---|---|
| Auxiliary ratio and connection | Voltage relationship at defined ports and taps | Zero-sequence impedance and short-time neutral duty |
| Auxiliary load/loss assessment | Response for the defined auxiliary excitation and load | Additional earth-fault section currents |
| Grounding-port impedance | Defined zero-sequence response at stated frequency and current | Full internal thermal and mechanical withstand |
| Short-time grounding-duty evidence | Assessed event at its stated initial condition and connection | Hotter or differently loaded simultaneous state |
| Combined-state assessment | Interaction under the specified simultaneous duties | Unexamined event sequences or altered cooling |
Record terminals, neutral state, auxiliary connections, frequency, current basis and starting temperature beside every result. A numerical comparison between tests is meaningful only after those conditions are reconciled.
Map combined currents into sections
In a linear electrical model, an identified section’s waveform can be written i(t) = iaux(t) + iground(t) with consistent reference directions. Its elementary conductor heating is proportional to i(t)²R, using resistance R in ohms and current in amperes. Expanding the square gives the two individual squared terms plus 2iauxiground.
The cross term cannot be discarded automatically for an individual section. In some symmetrical aggregate cases, terms can cancel across phases or average appropriately over time; that conclusion requires the actual connection, phase relationships and averaging interval. It does not establish the hottest section by itself.
The auxiliary load also sets the pre-fault thermal state. A grounding event beginning after steady auxiliary service may produce a higher final local temperature than the same event beginning from a cooler test state. Preserve that starting condition before claiming equivalence.
Check the combined duty at the governing section
Locate the section with the largest credible combined current or heat demand. It may differ from the section governing auxiliary-only operation. Include local joints, delta circulation where applicable, leakage-field loss and cooling restrictions in the design assessment.
For mechanical duty, use the combined relevant peak-current and field distribution. An auxiliary kVA value added to a short-time grounding kVA value does not reconstruct those forces or their duration.
Identify the evidence gap precisely
If the available factory record covers auxiliary ratio, ordinary loss and a low-current zero-sequence measurement, say so. The unresolved item may be the combined hot-start transient or a particular section’s fault force, not the whole transformer indiscriminately.
Retain the valid auxiliary and grounding results, then qualify the missing combined hot-start state by test or a justified equivalence assessment. Focus the additional evidence on the governing section’s thermal or mechanical duty.
Resolve the combined-current heating before release
Specify the earthing-transformer function and its test boundary under the applicable reactor standard [2].
Assume a 50 Hz section current of 20 A RMS from auxiliary duty and 100 A RMS from grounding duty, in phase, with 0.020 Ω section resistance at the starting temperature. Separate estimates give (20² + 100²) × 0.020 = 208 W; the combined waveform gives 120² × 0.020 = 288 W, 38.5% higher. Qualify the combined hot-start section duty rather than adding independent test losses.
References
- D. De Ronde, R. VanHatten and A. Wade, Loss of Effective System Grounding — Best Practices, Protection Challenges, and Solutions, Schweitzer Engineering Laboratories, 2015.
- IEC, IEC 60076-6:2007, Power transformers — Part 6: Reactors.