Calibrating Petersen-Coil Inductance against Plunger Position

  • Chenfan Power

Plunger travel is a mechanical coordinate. Electrical compensation follows the coil characteristic, which can change sharply near the travel limits. Calibrate inductance or compensation current against measured position so the controller commands the electrical duty the network actually requires.

The A. Eberle operating manual identifies coil-position linearization as part of controller configuration. That product function does not replace the coil-specific evidence needed to establish the actual position-to-response relation.

Calibrating Petersen-Coil Inductance against Plunger Position: technical review table
Record both directions at the same positions

Choose the electrical quantity being calibrated

At a stated frequency, voltage and magnetic condition, record the complex coil-port impedance Z = V/I. RMS phasor voltage V is in volts, current I is amperes and Z is ohms. A series-equivalent inductance is Lseries = Im(Z)/ω, with ω = 2πf in radians per second and Lseries in henries.

This is an equivalent at the measurement conditions. Tuning may instead use the branch’s inductive susceptance or its compensating current at a stated neutral voltage. Loss makes series and parallel equivalent values differ. Do not compare a controller’s parallel-model parameter with a series inductance unless the conversion and assumptions are explicit.

Record both directions at the same positions

Calibration fieldPurpose
Physical coordinate and indicated positionPreserves the distinction between plunger travel and sensor scaling
Approach directionExposes a direction-dependent response
Frequency and applied voltageDefines the electrical and magnetic measurement condition
Complex voltage and currentSupports the chosen impedance or admittance calculation
Temperature and settled-state criterionMakes resistance and repeated readings comparable
Repeat spread and uncertaintyDistinguishes a curve feature from measurement variation

Use enough positions to resolve curvature, including the ends of the approved working range. A few evenly spaced readings may miss a steep endpoint region. Repeat selected positions after approaching from each direction, retaining the same settling criterion and electrical conditions.

An increasing insertion coordinate often increases inductance in a particular plunger construction, but the sign must follow the actual geometry and position definition. A controller’s percentage coordinate may run in the opposite direction from physical insertion.

Make interpolation preserve the measured behavior

Plot the two directional curves and their repeat bands. Where the response is monotonic within uncertainty, a monotonic interpolation avoids invented overshoot between measured points. Near a steep end region, assess whether position uncertainty translates into an unacceptable compensating-current uncertainty before treating the last coordinate increment as equivalent to a middle-range increment.

For two readings Lup and Ldown at the same coordinate, report their difference together with acquisition uncertainty. A difference can arise from transmission play, sensor behavior, magnetic history or settling. The calibration exposes it; it does not by itself identify the mechanism.

Convert a lossy series equivalent before comparing controller data

Assumptions: the measured coil-port impedance at 50 Hz is 100 + j314.159 Ω, with the reactive term treated as 100π Ω for this calculation. Series-equivalent inductance is X/ω = 1.000 H. For the equivalent parallel branch, Lp = (R² + X²)/(ωX) = 1.1013 H, 10.13% higher [1]. These two numbers describe the same assumed port, rather than contradictory calibrations. Match the controller’s declared model and voltage/current reference [2], then compare directional position curves and their uncertainty on that common basis.

A usable calibration states the position reference, electrical quantity, test conditions and direction of approach. Keep the measured uncertainty visible in the fitted curve and verify the travel regions that govern the usable compensation range.