Neutral displacement changes phase-to-earth voltages while line-to-line voltages may remain near normal. Reconstruct each grounding-transformer section’s induced voltage and ampere-turn balance to determine the limb flux under that state. [1]
Calculation basis. Project-specific values and gates in the illustrative screens below are assumptions; cited catalogue values retain their source test conditions.
For a symmetrical zigzag, equal zero-sequence currents produce opposing limb ampere-turns. A displaced neutral therefore cannot be translated into a core-flux increase by simply applying the phase-to-earth voltage to every half-winding. Nor does ideal cancellation exclude leakage-field effects, section asymmetry or another simultaneously excited winding.

Reconstruct the induced voltage of each section
For a section linking a defined limb flux, eind = sN dΦ/dt, where s is its polarity sign, N is series turns, Φ is flux in webers and time is in seconds. The induced voltage eind is in volts. Its relationship to measured section terminal voltage must include the section’s resistive drop and the leakage-flux contribution represented by the chosen model.
Using a consistent sign convention, integrate Φ(t) = Φinitial + (1/(sN))∫eind(t)dt. The initial flux is an input, not a value automatically recovered from the voltage integral. If flux density is needed, B = Φ/Aeff with B in teslas and effective magnetic cross-sectional area Aeff in square metres.
| Required input | Role in the reconstruction | Failure if omitted |
|---|---|---|
| Actual section turns and polarity | Maps volts to the identified limb flux | Wrong sign or scale |
| Section induced voltage | Drives the flux integral | Terminal drops mistaken for core excitation |
| Initial magnetic state | Sets the integral offset | Unknown peak flux even with a correct change |
| Core return-path model | Constrains coupled limb fluxes | Arbitrary independent limb results |
Resolve the section voltages behind the terminal waveform
In an ideal signed zigzag representation, a phase’s induced voltage combines flux derivatives from two different limbs. Those difference relationships do not independently identify every possible common magnetic component. The common component requires the magnetic return-path constraints and excitation balance, not another copy of the same terminal line-voltage measurement.
Under real asymmetry, unequal turns or currents can leave a residual limb magnetomotive force. Additional return limbs, joints, tank paths and air regions influence how that residual produces flux. A core model appropriate to one construction may misrepresent another unit with the same terminal connection designation.
Compare a displaced-neutral case with its normal baseline
Use the same geometry and magnetic characteristic for the normal and displaced cases. Add the actual unbalanced voltage components, section currents and initial state. Plot each limb’s flux trajectory and mark where its nonlinear response becomes material. Do not select an unrelated universal flux-density number as the saturation limit.
Identify the section-voltage and magnetic-state inputs needed to reconstruct the displaced-neutral flux. Use the terminal waveforms to define the next measurement or model check and retain the matched normal-state baseline.
Check what the reconstructed trajectory asks of the steel
The earthing-transformer connection determines the section-voltage boundary [2]. Nippon Steel’s 23ZH90 loss ceiling is 0.90 W/kg at 1.7 T, 50 Hz under catalogue conditions [3]. Use that point to identify the available material evidence, rather than inventing a universal saturation threshold.
Assume a model gives an initial 0.20 T for one identified limb, 100 section turns and 0.010 m² effective area. Its signed integral reaches +1.30 V·s in the normal case and +1.65 V·s in the displaced-neutral case. The corresponding flux densities are 0.20+1.30/(100×0.010)=1.50 T and 0.20+1.65/(100×0.010)=1.85 T. The latter is 23.3% higher. These are specified trajectory samples; inspect the complete cycle to locate the actual peak.
The 1.85 T sample already lies outside the cited 1.7 T loss point. Obtain the relevant nonlinear characteristic, section-voltage waveform and initial state before predicting current or losses. A normal line-to-line voltage reading cannot replace this limb reconstruction. Match joint overlap, cut-edge stress, burr condition and clamp loading to the core used for the magnetic evidence.
References
- D. De Ronde, R. VanHatten and A. Wade, Loss of Effective System Grounding — Best Practices, Protection Challenges, and Solutions, Schweitzer Engineering Laboratories, 2015.
- IEC, IEC 60076-6:2007, Power transformers — Part 6: Reactors.
- Nippon Steel Corporation, Grain-Oriented Electrical Steel Sheets, catalogue D004je, April 2020, specification and typical-property tables.