Zigzag leakage reactance depends on the coupling of its six winding sections and the imposed current pattern. Model the two-limb path of each phase and the opposing sections on each limb before extracting the impedance seen at the grounding port. [1]
Calculation basis. Project-specific values and gates in the illustrative screens below are assumptions; cited catalogue values retain their source test conditions.
Start with the zero-sequence port that the system study actually needs. A per-phase sequence impedance and the impedance seen by a source connected between bonded line terminals and neutral are related quantities, with different current bases.

Define the port before fitting an inductance
For a symmetrical unit, bond the three phase terminals conceptually into one test node. This is a model definition, not a field connection instruction. If the applied voltage from that node to neutral is Vtest and the total current is Itest, each phase carries I0 = Itest/3. The per-phase zero-sequence impedance is Z0 = Vtest/I0 = 3Vtest/Itest. The measured single-port impedance is Zport = Vtest/Itest = Z0/3.
Voltages and currents here are same-frequency RMS phasors in volts and amperes; impedances are in ohms. Keep any external neutral resistor outside the transformer model. Including it in the measurement without correction changes the quantity being fitted.
Retain the six-section coupling
Represent the six winding sections by a resistance matrix R and an inductance matrix L, referred to their own signed section currents. Diagonal inductances alone are inadequate because mutual terms determine how opposing ampere-turns affect stored energy. The geometric calculation must include the section positions, conductor regions and relevant leakage-field return paths.
Let q be the six-element vector mapping the total test current into section currents: i = q Itest. For the simple symmetrical series arrangement, every section has magnitude Itest/3; q therefore contains signed thirds according to the selected current-reference convention. In a linear model, Lport = qᵀLq. L is in henries, q is dimensionless and Lport is in henries. This follows from magnetic energy W = ½iᵀLi, with instantaneous currents in amperes and W in joules.
| Model stage | Quantity retained | Reconciliation check |
|---|---|---|
| Section geometry | Six self terms and mutual couplings | Current references agree with the polarity drawing |
| Zero-sequence projection | q with signed section-current fractions | Three phase currents sum to Itest |
| Single-port result | Rport and Lport | Zport agrees with the defined bonded-terminal measurement |
| System-study export | Z0 = 3Zport | External neutral impedance remains separately identified |
Validate the model over the required current range
For a lossless inductive part, Xport = 2πfLport, where f is frequency in hertz and Xport is in ohms. Actual measurements can contain conductor loss, stray loss and nonlinear excitation. A complex fitted impedance may reproduce a test point without validating the physical loss distribution inside the unit.
Compare calculated and measured complex impedance at matched frequency, temperature and current. Investigate current-dependent disagreement through ampere-turn balance and the nonlinear magnetic paths, then validate the model across the required fault-current range.
Expose the mutual terms in a six-section calculation
Assume a linear 50 Hz model. Order the sections as three same-limb opposing pairs. Each pair has self-inductances 6 mH and mutual inductance +5 mH on dotted-terminal references; neglect coupling between different pairs for this demonstration. The signed zero-sequence projection is q=(1,−1,1,−1,1,−1)/3. The pair matrices are positive definite, with eigenvalues 11 mH and 1 mH.
Then Lport = 3(6+6−2×5)/9 = 0.6667 mH. At 50 Hz, Xport = 0.2094 Ω and X₀ = 3Xport = 0.6283 Ω. At 30 A instantaneous port current, stored energy is 0.300 J. Omitting the mutual terms gives Lport = 4.000 mH and X₀ = 3.770 Ω: a sixfold impedance error in this assumed model.
Retain the actual signed mutual matrix when reconciling section geometry with a bonded-terminal measurement. The earthing-transformer test connection remains a separately specified boundary [2]. This example tests the projection and current basis; determining the actual matrix still requires the real geometry or matched impedance evidence.
References
- D. De Ronde, R. VanHatten and A. Wade, Loss of Effective System Grounding — Best Practices, Protection Challenges, and Solutions, Schweitzer Engineering Laboratories, 2015.
- IEC, IEC 60076-6:2007, Power transformers — Part 6: Reactors.