Reconnection links can set the usable current of a mobile transformer’s voltage mode. Trace the conductors, contact interfaces and shared joints carrying current in each connection, then assess their local heating and fault duty alongside the winding rating. [1]
Calculation basis. Project-specific values and gates in the illustrative screens below are assumptions; cited catalogue values retain their source test conditions.

Map link current in every connection
Use the actual mode drawings to determine which links carry line current, section current or a combination of branch currents. Preserve phase direction and branch allocation. A link that is unused in one mode can carry a critical current in another; a nominal winding current is not a substitute for that path calculation.
| Mode-specific item | Current evidence | Thermal and mechanical evidence |
|---|---|---|
| Individual reconnection link | Circuit-derived RMS and relevant waveform | Conductor section, AC effects and heat path |
| Contact interface | Actual current crossing the mating surfaces | Contact resistance, force and temperature distribution |
| Shared or branching connection | Branch phasors and the resulting link current | Unequal sharing and local heat concentration |
| Link near supports or insulation | Same current with actual local geometry | Cooling obstruction and adjacent material temperature |
| Fault-duty state | Relevant peak and current-time history | Contact retention and conductor force/thermal capability |
Quantify why a joint can control the result
For an illustrative interface carrying 800 A RMS, an assumed resistance of 50 μohms produces I²R = 32 W. If that resistance becomes 100 μohms at the same current, the loss becomes 64 W. This calculation is local electrical heating, not a temperature-rise prediction. Contact geometry, conduction into the links and surrounding liquid flow determine the temperature response.
Use resistance measured or justified at relevant conditions. Contact load, surface condition, assembly variation and temperature can change it. At non-sinusoidal current, frequency-dependent effects and current paths may require more than a single DC resistance.
Define the link current and duty envelope
Connect each permissible mode to its link-current result, joint evidence and thermal boundary. Include the actual cooler deployment because a contact near a restricted liquid route may respond differently from the main winding. Evaluate repeated reconnection where it changes the contact condition.
Separate continuous heating from short-circuit duty. A link with adequate steady thermal behavior may require additional evidence for peak force or short-time heating, and a fault withstand statement does not establish a continuous current rating.
Name the connection that controls each mode and attach its thermal and fault-duty evidence. A mode-current matrix gives the buyer a clear usable rating for the assembled unit.
Compare link-joint loss under two contact states
Keep the contact and cooling condition tied to the installed link [2].
At the assumed 800 A RMS duty, 50 μΩ gives 32 W and 100 μΩ gives 64 W. For an assumed 40 W local loss budget in this screen, the two resistance states give current screens of 894.4 A and 632.5 A. Qualify the joint geometry and cooling before placing either current on the mode rating sheet.
References
- U.S. Department of Energy, DOE-HDBK-1011/4-92, Electrical Science, Volume 4, 1992.
- U.S. Bureau of Reclamation, FIST Volume 3-30, Transformer Maintenance, 2000.

