ARTICLETechnical article

Loss Allocation across Phase-Shifter Tap States

  • Chenfan Power

Phase-shifter loss allocation changes with tap and power-transfer state. Map regional sources in the series and excitation units with their cooling boundaries to identify the local duty behind each total loss. [1]

Calculation basis. Project-specific values and gates in the illustrative screens below are assumptions; cited catalogue values retain their source test conditions.

State what is held constant in the comparison. Receiving-end active power, terminal voltage and power factor define a different boundary from constant current or constant nameplate MVA. If those inputs change, report that change rather than attributing every loss difference to tap alone.

Loss Allocation across Phase-Shifter Tap States: technical review table
Allocate loss by unit and tap state

Allocate loss by unit and tap state

Loss regionInput to preserve across the comparisonOutput needed
Series-unit winding conductorsActual internal current spectrum and temperatureConductor loss within its defined model
Excitation-unit winding conductorsTap-dependent branch currents and couplingLocal loss rather than terminal-current substitution
Each core/excitation regionApplicable voltage waveform and magnetic modelExcitation loss under the actual state
Tank/clamps and other structureComplete coupled field and material geometryRegion-specific stray loss
Intertank connectionsActual route currents and effective resistanceAssembly loss without unit double counting
Cooling/auxiliary boundaryActual auxiliary states and heat partitionConsistent system total and local heat removal

Keep current and power references consistent

For balanced receiving-end fundamental power, Iline = P/(√3VLLcosφ) under the stated boundary. Keeping P constant while voltage or power factor changes does not keep current constant. Internal winding currents require the actual topology mapping beyond this external relation.

A restricted conductor sum is Pcu = Σk,h Ik,h,rms²Rk,h, with each effective resistance tied to its geometry, frequency and temperature. Coupled field terms need an appropriate model; separately adding a loss already included in effective resistance would double count.

Compare local thermal consequences

Equal total loss can coexist with more heat in one unit and less in another. The temperatures depend on each region’s cooling path and thermal state. A total-watts comparison therefore cannot establish unchanged internal thermal margins.

Retain the actual cooling configuration and initial condition when comparing taps. Series and excitation units need not have identical thermal behavior. Their connections can also conduct heat across a boundary, so model partition and heat-removal partition are related but not identical.

Reconcile with the measured boundary

Use applicable test data at known taps and temperatures to validate the included loss terms. A whole-device result can support a total while leaving its internal allocation uncertain. Preserve that distinction rather than inventing unit loss percentages to complete a table.

Across the credited tap range, identify the region that governs local temperature or another component constraint. If only total rated loss is available, state the missing partition evidence.

Pair every evaluated tap and transfer state with regional heat sources and cooling. Use that map to show the local duty alongside total loss.

Compare equal total loss with different regional temperatures

Assume two 50 Hz tap states at the same specified through-current duty. In a simplified regional heat model, neutral tap allocates 30 kW to the series unit and 20 kW to the excitation unit; an extreme tap allocates 40 kW and 10 kW. Both total 50 kW. Actual internal-current mapping must come from the PST design [1][2].

Assume independent steady thermal paths to a 40 °C boundary, with series-unit resistance 0.5 K/kW and excitation-unit resistance 0.8 K/kW [3]. Neutral-state node temperatures are 55 °C and 56 °C; extreme-state temperatures are 60 °C and 48 °C. Against an assumed 58 °C series-node limit, neutral passes and the extreme state fails despite unchanged total loss.

Obtain regional losses and matched cooling evidence across the credited tap duty. These assumed nodes illustrate heat allocation; they do not represent winding hotspots or a measured transformer temperature map.

References

  1. B. Cook, M. J. Thompson, K. Garg and M. Malichkar, Phase-Shifting Transformer Control and Protection Settings Verification, 2018. DOI: 10.1109/CPRE.2018.8349815.
  2. IEC, IEC 62032:2012, Guide for the Application, Specification and Testing of Phase-Shifting Transformers.
  3. U.S. Department of Energy, DOE-HDBK-1012/2-92, Thermodynamics, Heat Transfer, and Fluid Flow, Volume 2, 1992.