An intertank connection’s delay and coupling matter when they approach the studied transient timescale. Use its length, return paths and event timescale to select the connection model for the assembled phase shifter. [1]
Calculation basis. Project-specific values and gates in the illustrative screens below are assumptions; cited catalogue values retain their source test conditions.
Identify every conductor, return and shield or bonding path in the actual connection. A single isolated-cable parameter cannot represent coupled three-phase or common-mode behavior without justification.

Choose the connection model by bandwidth
| Model input | Evidence required | Effect on the transient boundary |
|---|---|---|
| Installed length and route | Final geometry rather than transport drawing | Propagation time and coupling |
| Per-unit-length parameters | Applicable R,L,C,G and frequency range | Loss, delay and characteristic behavior |
| Returns/shields/grounding | Actual continuity and terminations | Common-mode paths and coupled voltages |
| Unit terminal models | Wideband series/excitation-unit behavior | Reflection and internal stress depend on both ends |
| Waveform range | Rise time and relevant spectrum | Whether lumped approximation is justified |
| Validation evidence | Suitable measurements and uncertainty | A fitted low-frequency equivalent may miss fast behavior |
Estimate the propagation scale explicitly
For a restricted lossless single-mode line, delay is τ = ℓ√(L′C′), and characteristic impedance is Z0 = √(L′/C′). With illustrative L′ = 0.4 µH/m, C′ = 0.1 nF/m and ℓ = 20 m, τ is 126.5 ns and Z0 is 63.25 Ω.
These assumed parameters are not a cable specification. Compare the delay with the studied rise time and frequency range before choosing a lumped model. The appropriate approximation requires an error assessment, not a universal cable-length cutoff.
Retain the terminal reflections
In the same ideal line model, a termination has reflection coefficient Γ = (Zload − Z0)/(Zload + Z0) under consistent impedance definitions. An ideal open termination has Γ = +1, but a real transformer terminal is not assumed open. Its frequency-dependent response defines the actual reflection.
The series and excitation units can exchange transient energy through several paths. Include their actual terminal and grounding relationships instead of connecting the cable to arbitrary lumped capacitances solely to obtain a waveform.
Validate the requested internal-voltage result
Use a coupled or frequency-dependent connection model where required by the geometry and bandwidth. Retain the parameter extraction method and range. Passivity and time-domain consistency need appropriate checks before a fitted model is used to predict peaks.
Compare accessible terminal responses or other suitable evidence without claiming direct inspection of every internal winding location. A match at low frequency cannot independently validate high-frequency overvoltage. Transformer prestrike research treats terminal and internal winding response as distinct validation quantities [2].
Carry demonstrated intertank-length sensitivity into the installed transient model. Join separate-unit evidence through the actual connection and its waveform boundary.
Choose the model on the event timescale
For the assumed 20 m connection above, delay is 126.5 ns. Against a 100 μs current transition, delay is 0.1265% of the rise time. A lumped 20 μH connection carrying an assumed 2 kA change over that interval gives Ldi/dt = 400 V; at 500 μs it gives 80 V. Confirm the requested model error and actual return geometry before using that approximation [3].
A separate assumed 50 ns voltage front is shorter than the line delay: τ/trise = 2.53. An instantaneous lumped connection cannot reproduce that arrival sequence. Use a distributed connection and compatible wideband unit-terminal models for that case [2]. Do not extrapolate the 20 μH slow-transition calculation into an internal fast-front peak.
References
- B. Cook, M. J. Thompson, K. Garg and M. Malichkar, Phase-Shifting Transformer Control and Protection Settings Verification, 2018. DOI: 10.1109/CPRE.2018.8349815.
- M. Popov, R. P. P. Smeets, L. van der Sluis, H. de Herdt and J. Declercq, Experimental and Theoretical Analysis of Vacuum Circuit Breaker Prestrike Effect on a Transformer, IEEE Transactions on Power Delivery 24, 2009. DOI: 10.1109/TPWRD.2009.2013383.
- IEC, IEC 62032:2012, Guide for the Application, Specification and Testing of Phase-Shifting Transformers.