Phase-shifter through-current capability follows the internal winding duty across taps and power directions. Map those relationships to identify the component governing each operating state. [1]
Calculation basis. Project-specific values and gates in the illustrative screens below are assumptions; cited catalogue values retain their source test conditions.
Identify the measured through-current reference, terminal voltage and power direction. Then obtain the internal mapping for the actual connection and tap. A model inferred from another two-unit design can assign the wrong current to the controlling winding.

Build a tap-and-direction current map
| State field | Evidence to map | Constraint to preserve |
|---|---|---|
| Tap/injection state | Actual connection and angle relationship | Internal current factors and winding voltage |
| Through-current boundary | Line/phase and referred-side definition | Correct comparison with terminal capacity |
| Power direction and power factor | Actual current phasor relative to voltage | Internal duty need not mirror at reversal |
| Each internal winding | Validated current and loss at the state | Local thermal or other component limit |
| Cooling/temperature state | Applicable local heat-removal condition | Current limit belongs to the qualified state |
| Transition or abnormal state | Actual temporary current path where relevant | Steady tap map may not bound every event |
Retain the basis of each internal-current factor
For illustration, suppose a simplified winding current is Ik = a(tap)Ithrough, ignoring excitation and other coupled terms only in this example. Assume its permitted comparison current is 700 A. At an assumed factor 0.6, a 1000 A through-current gives 600 A internally. At factor 0.9 it gives 900 A.
The second assumed state exceeds that invented comparison boundary. Under the same restricted mapping, its through-current bound would be 700/0.9 = 777.8 A. These factors and currents are not product data, ratings or operating allowances.
An actual mapping can include excitation, several internal branches and phase-dependent terms. The controlling limit is obtained from that supported model and qualified local duty, not by adopting the example’s scalar factor.
Compare limits on the same state
Check terminal, internal winding, tap-changer and relevant structural/thermal boundaries at each credited tap and power direction. A nominal through-power comparison can conceal a local constraint because internal currents are not all identical to terminal line current.
Retain voltage magnitude as well as current. The relationship S = √3VLLIline applies to balanced apparent power at the declared external boundary; it does not independently calculate every internal component duty.
Specify a supported operating envelope
Record confirmed limits and unqualified regions separately, with the temperature/cooling basis. Interpolate only where a supported model justifies it. A nominal tap result should not be extended to the extremes by assumption.
State the internal limiting mechanism and its through-current consequence for the relevant model. Keep reverse and transition states identified with their demonstrated or unresolved coverage.
Carry the limiting winding into the external power envelope
Continue the assumed 700 A internal comparison boundary and factors 0.6 and 0.9. They imply through-current bounds of 1,166.7 A and 777.8 A respectively. Assume another terminal-current limit of 1,000 A RMS, with 220 kV line-to-line in the first state and 210 kV in the second, at 50 Hz.
The binding currents are therefore 1,000 A and 777.8 A. Their balanced three-phase apparent powers are √3×220 kV×1.000 kA = 381.1 MVA and √3×210 kV×0.7778 kA = 282.9 MVA, a 25.8% reduction. The second state is governed by the internal winding, not the assumed terminal-current limit. The PST application envelope must retain that actual component mapping [2].
References
- B. Cook, M. J. Thompson, K. Garg and M. Malichkar, Phase-Shifting Transformer Control and Protection Settings Verification, 2018. DOI: 10.1109/CPRE.2018.8349815.
- IEC, IEC 62032:2012, Guide for the Application, Specification and Testing of Phase-Shifting Transformers.