Unequal Taps in Parallel Phase-Shifting Transformers

  • Chenfan Power

Unequal parallel phase-shifter taps create a loop-voltage mismatch and circulating current. Solve each branch and internal current with the physical mismatch, impedance and control state to establish the permitted combination. [1]

Calculation basis. Project-specific values and gates in the illustrative screens below are assumptions; cited catalogue values retain their source test conditions.

Draw the shared terminals and actual tap transformations. Confirm angle signs, voltage magnitudes and the circulating path before applying a parallel-branch equivalent. A matched tap number is not proof of a matched physical angle across different devices.

Unequal Taps in Parallel Phase-Shifting Transformers: technical review table
Separate transfer and circulation

Separate transfer and circulation

For a restricted pair of equivalent voltage sources behind series impedances, Icirc = (E1 − E2)/(Z1 + Z2), with consistent source polarity and loop direction. The branch currents also contain the network transfer components. Magnitudes cannot be added or subtracted as ordinary scalar loads.

Illustratively, let the two equivalent source magnitudes be 1 per unit with a 2° angle difference, and let |Z1 + Z2| = 0.20 per unit on the same base. The mismatch magnitude is 2sin1° = 0.03490 per unit, giving |Icirc| = 0.1745 per unit in this restricted loop.

The assumed result is not a permissible tap mismatch. Real unequal ratios, tap-dependent impedances and network states require the actual model; each internal current constraint must still be checked.

Parallel-state questionEvidence to retainConstraint that can be hidden
Angle and magnitude mismatchActual terminal transformations on common referencesCirculation can exist before intended transfer is added
Loop impedanceTap-dependent complex equivalents and actual routeSmall mismatch can produce significant branch current
Branch current splitComplete phasor solution and power directionTotal flow does not establish each branch loading
Internal current/thermal mapEach device at its actual tapA terminal current may conceal another local limit
Control responseCommands, feedback and timing for both unitsControllers can chase each other or increase mismatch

Verify coordination across the parallel operating states

Two controllers acting on the same corridor target need a defined coordinated objective and response. A delayed tap indication or differing sensitivity can lead each controller to compensate for the other’s action. Record actual state completion instead of treating a command as an achieved tap.

Check both steady mismatch and authorized transition states in the study. The two units may not move simultaneously, and a temporary mismatch can govern a constraint. The permissible mismatch depends on the actual branch and internal-current constraints.

Qualify the parallel state on the full branch and internal current solution and supported control behavior. Address the governing mismatch and loop impedance when circulation sets the limit.

Use the actual PST connection and tap envelope when assessing parallel states [2].

References

  1. B. Cook, M. J. Thompson, K. Garg and M. Malichkar, Phase-Shifting Transformer Control and Protection Settings Verification, 2018. DOI: 10.1109/CPRE.2018.8349815.
  2. IEC, IEC 62032:2012, Guide for the Application, Specification and Testing of Phase-Shifting Transformers.