Tap-dependent phase-shifter matrices must preserve terminal transformation and internal-equivalent changes. Record those effects separately with the port convention to reproduce the selected terminal states. [1]
Calculation basis. Project-specific values and gates in the illustrative screens below are assumptions; cited catalogue values retain their source test conditions.
Define all ports, current directions and reference bases first. A reduced positive-sequence bus model is different from a physical multiwinding electromagnetic model. Its matrix properties should be checked under its own representation rather than borrowed from an ordinary two-winding transformer.

Track matrix definitions across taps
| Parameter record | Definition to preserve | Validation comparison |
|---|---|---|
| Port list and current signs | Internal or external terminal identities | No silent port permutation between tap states |
| Complex ratio | Magnitude, angle and from/to convention | Measured terminal relationship and software sign |
| Series/multiport equivalent | Referred base, R/X and applicable frequency | Actual test boundary for each parameter |
| Tap extremes and intermediate states | Actual matrix or supported parameter rule | No unsupported constant-impedance extension |
| Reduction constraints | Neutral, open/closed winding and eliminated ports | Reduced matrix reproduces the intended connection |
| Consistency checks | Power balance, loss and applicable network properties | Model errors separated from representation differences |
See tap dependence in a simple terminal model
For a declared no-shunt branch with series admittance y and from-side complex tap t = τexp(jφ), one conventional bus-admittance model is Yff = y/|t|², Yft = −y/t*, Ytf = −y/t and Ytt = y. The asterisk denotes complex conjugation.
Even if y is unchanged, a changed φ alters the off-diagonal terms. For nonzero phase angle, Yft and Ytf are generally different. Blindly forcing this reduced matrix to equal its transpose can remove the intended phase shift.
This is an explicitly declared software-style equivalent, not the internal circuit of every PST. The actual equipment’s tap-dependent series and multiport parameters require additional topology/test evidence.
Check loss and port behavior
Use representative voltage/current states to verify power balance and the included dissipative loss. A sign or conjugation error can create physically inconsistent results even when one no-load ratio looks correct.
Apply symmetry or reciprocity checks only where appropriate to the actual representation and physical assumptions. A property of an unreduced winding network need not appear as simple transpose symmetry after complex-ratio and sequence reduction.
Validate the extreme states deliberately
Compare supported factory measurements with the model at angle endpoints and representative intermediate taps. Retain test uncertainty, frequency and connection boundaries. Catalogue abstracts about measurement-based models do not supply missing matrix values.
Deliver the matrix record with reproducible port conventions, verified tap states and identified parameter uncertainty. Obtain missing tap data before extending the representation.
Verify the off-diagonal terms with a complex tap
Retain the tested PST tap and connection boundary when validating the matrix [2].
Assume a unit-magnitude tap a = eʲ¹⁰° and branch admittance y = −j5 per unit, with no shunt. Using the declared from-side tap convention gives Yff = −j5 and Yft = −y/conj(a) = −0.86824 + j4.92404 per unit. Preserve the conjugate in the opposite off-diagonal term; copying one off-diagonal entry into the other violates this declared phase mapping.
References
- B. Cook, M. J. Thompson, K. Garg and M. Malichkar, Phase-Shifting Transformer Control and Protection Settings Verification, 2018. DOI: 10.1109/CPRE.2018.8349815.
- IEC, IEC 62032:2012, Guide for the Application, Specification and Testing of Phase-Shifting Transformers.