Symmetrical and asymmetrical phase-shifter concepts change angle and magnitude differently. Compare their phasors with current and series impedance to establish terminal voltage across the required loaded states. [1]
Calculation basis. Project-specific values and gates in the illustrative screens below are assumptions; cited catalogue values retain their source test conditions.
Use the actual manufacturer’s topology when classifying equipment. The geometries below are declared idealized phasor constructions for reasoning, not internal drawings of a supplied transformer.

Compare two ideal voltage constructions
For an equal-magnitude symmetrical construction, take VS = Vexp(−jα/2) and VR = Vexp(+jα/2). Their difference is 2jVsin(α/2), perpendicular to the midpoint phasor Vcos(α/2). The two ideal endpoint magnitudes are equal.
For a restricted asymmetrical construction, take VS = V and VR = V + jqV. Then α = arctanq and |VR|/|VS| = √(1+q²) = secα within the stated angle range. The quadrature injection is perpendicular to the input reference, rather than the midpoint construction above.
| Comparison field | Equal-magnitude ideal construction | Input-quadrature ideal construction |
|---|---|---|
| Injection reference | Midpoint voltage direction | Input voltage direction |
| No-load endpoint magnitudes | Equal by the stated geometry | Output magnitude increases with nonzero q |
| 20° illustrative shift | Injection magnitude 0.3473 times the endpoint voltage V | q=0.3640; output/input magnitude 1.0642 |
| Loaded terminals | Include actual series drop and current | Include actual series drop and current |
| Actual equipment | Verify its topology and model | Verify its topology and model |
Include the load-current phasor
In a restricted series equivalent, loaded output is VR,load = VR,ideal − ZseriesI with declared polarity. Its magnitude and angle depend on the current direction and power factor as well as the ideal injected voltage. Equal no-load magnitudes do not guarantee equal loaded magnitudes.
Compare lagging, leading and reversed-power states using the supported internal model. The same current magnitude can give another voltage drop vector. A fixed-current phasor sensitivity is also different from a complete load-flow solution in which current and bus voltage change together.
Keep tap and internal constraints visible
The injection and impedance can depend on tap. Retain internal winding voltages and current limits when comparing terminal performance; a phasor geometry alone does not qualify those parts. Actual designs may include additional regulating or connection features.
Use consistent winding/line and referred-voltage bases in the comparison. A measured terminal ratio should not be substituted directly for an internal injection ratio without the topology map.
Specify terminal magnitude and angle under the relevant loaded cases. Select the supported design and model that meet those requirements and internal duty.
Identify the actual PST construction before applying either idealized phasor model [2].
References
- B. Cook, M. J. Thompson, K. Garg and M. Malichkar, Phase-Shifting Transformer Control and Protection Settings Verification, 2018. DOI: 10.1109/CPRE.2018.8349815.
- IEC, IEC 62032:2012, Guide for the Application, Specification and Testing of Phase-Shifting Transformers.