Ultrasonic Dead Zones in Thin Transformer Tank Welds

  • Chenfan Power

In a thin tank weld, a pulse can return from the backwall quickly while the instrument is still resolving the initial response or another echo. Joint geometry adds further reflections. A successful scan motion does not show that every depth was examined with useful sensitivity. [1]

Ultrasonic Dead Zones in Thin Transformer Tank Welds: technical review table
First article table, reproduced without adding or changing values. See the article for assumptions and application boundaries.

Compare the timing scales

For a simple normal-beam path through thickness d, round-trip time is t = 2d/c, using metres and acoustic speed c in m/s to obtain seconds. Compare this with the effective pulse and system resolution. An angled beam follows a different path; use its actual geometry.

The relation is a screening check only. Probe ringing, wedge response, surface condition, focus and weld geometry determine the demonstrated dead zones. A catalogue frequency alone does not establish them.

RegionPotential limitationEvidence to retain
Entry surfaceInitial pulse/wedge responseDemonstrated near-surface sensitivity
Root/backwall regionEcho overlap and joint reflectionsRepresentative reference response
Corner/attachmentBeam access and geometric indicationPath map and classification
Unresolved length/depthOutside demonstrated capabilityComplementary inspection or process evidence

Choose NDT using material, weld thickness, welding process, quality requirements and demonstrated coverage. NDT acceptance levels are not a detailed one-to-one translation of weld quality levels. [2]

Calculate the available echo separation

Assume a 4 mm normal-beam steel path at 20 °C with acoustic speed 5,900 m/s. Round-trip time is 2×0.004/5,900 = 1.356 μs. If the demonstrated instrument/probe dead interval is an assumed 2 μs, this backwall return lies inside it. Select and demonstrate a method that addresses the unresolved region; catalogue frequency alone is insufficient.

Demonstrate before assigning coverage

Use representative thickness, material and joint references under the qualified examination plan. Show that the feature of concern can be distinguished from the geometry. A flat calibration block may not represent a corner seam’s root response.

References

  1. U.S. Federal Highway Administration, Bridge Welding Reference Manual, FHWA-HIF-19-088, 2019.
  2. ISO, ISO 17635:2025, Non-destructive testing of welds — General rules for metallic materials.
Chenfan Electric