Parallel Air-Core Conductors: Resistance Is Only One Check

  • Chenfan Power

Air-core reactor field/circuit studies solve parallel coil currents and linked magnetic fields together. [1] Equal DC resistance alone cannot establish current sharing: different positions and lead paths change self and mutual inductances as well as resistance.

Label every parallel branch from terminal to terminal. For a linear fixed layout, write v = R i + L di/dt as a branch-vector equation, including self and mutual terms. Here v is in volts, i in amperes, R in ohms, L in henries and t in seconds. Branches connected to common terminals share terminal voltage, not necessarily current.

Parallel Air-Core Conductors: Resistance Is Only One Check: technical review table
First article table, reproduced without adding or changing values. See the article for assumptions and application boundaries.

Compare the complete branch paths

Path itemEvidencePossible imbalance
Conductor resistanceLength, section, joints and temperatureResistive voltage-drop mismatch
Coil positionSelf/mutual inductance matrixUnequal linked flux
TranspositionActual sequence of positionsIncomplete averaging of branch exposure
Terminal leadsLength, routing and nearby conductorsAsymmetry outside the nominal winding

Solve current sharing on the installed frequency basis

For sinusoidal operation, with ω in rad/s, Z = R + jωL. Solve the coupled branch equations with common-terminal constraints and total current. Check individual currents and losses; dropping mutual terms changes the model. [2]

A transposition can equalize exposure when it gives branches comparable time or length in the relevant positions. Verify the complete path; a winding transposition may leave asymmetric leads. Its adequacy also depends on the field geometry, not solely on equal conductor length.

Retain the complete branch path through the terminals when comparing a proposed transposition; equal conductor length does not alone equalize linked flux.

Compare branch current with unequal inductance

Assumptions: two parallel branches at 80 °C each have R = 0.020 Ω; at 50 Hz their L₁ = 1.0 mH, L₂ = 1.2 mH and signed M = +0.8 mH. Total current is 220∠0° A RMS. Equal terminal voltages give I₁ = 220[R + jω(L₂−M)]/[2R + jω(L₁+L₂−2M)]. Magnitudes are 145.28 A and 75.28 A; the phasors sum to 220 A. Against an assumed 130 A branch limit, branch 1 fails by 15.28 A. Setting M = 0 falsely predicts 119.97 A and 100.04 A. Hold the sharing claim and verify the installed coupled matrix. [2]

References

  1. J. Wu et al., Thermal Simulation and Analysis of Dry-Type Air-Core Reactors Based on Multi-Physics Coupling, Energies 16, 7456, 2023. DOI: 10.3390/en16217456.
  2. U.S. Department of Energy, DOE-HDBK-1011/3-92, Electrical Science, Volume 3, June 1992.