A valve-side lead support has to hold a conductor and coexist with its insulation field. Fasteners, material interfaces and support edges can concentrate electric stress; fault forces can then move the lead toward a barrier. Electrical and mechanical reviews must use the same geometry. Apply the HVDC transformer specification framework of IEC/IEEE 60076-57-129 to the stated liquid-immersed equipment [1].
Identify the lead voltage relative to earth and nearby windings for the actual converter state. Define support material, moisture condition, temperature and relevant electrical properties. For sustained DC, conductivity can matter in addition to permittivity. A room-temperature strength data sheet is not a complete support qualification. [2]

One support, several constraints
| Constraint | Evidence to retain | Interface risk |
|---|---|---|
| Electric field | Edges, fasteners, screens and material properties | Local concentration or unfavorable field sharing |
| Mechanical strength | Fault-force direction, support span and attachment | Fracture, slip or fastener movement |
| Displacement | Lead/support deformation under defined load | Reduced clearance to barrier or earth |
| Material ageing | Temperature, liquid exposure and retained properties | Electrical or mechanical behavior changes over time |
Translate force into a clearance question
For a screening geometry, calculate the lead displacement in the relevant load direction. Compare the displaced shape with the minimum insulation clearance, including assembly tolerances. A strength check that prevents fracture does not prove that displacement remains electrically acceptable.
Use the actual fault-current combination and force distribution. A generic support load applied at its centre may miss a moment transmitted by a conductor bend or terminal. The attachment and adjacent lead section form part of the mechanical load path.
Convert a support load into residual oil clearance
Assume a small-deflection cantilever screening model: transverse force 3 kN, free length 0.40 m, modulus 20 GPa and second moment of area 2 × 10⁻⁷ m⁴. Tip movement FL³/(3EI) is 16 mm. From a nominal 50 mm gap with 4 mm adverse assembly tolerance, the residual gap is 30 mm. Against an assumed project screening requirement of 35 mm, the shortfall is 5 mm. Shorten the span or increase stiffness, then recheck the changed electric-field geometry; the beam calculation alone cannot qualify the insulation.
Review fasteners as electrical features
Metallic attachment details can alter local field even when they sit outside the nominal conductor-to-earth line. Inspect their curvature, position and connection potential. A floating metallic part needs its potential defined by the model rather than assumed earthed.
Verify the support where field-critical regions intersect mechanically critical directions. Moving a fastener to improve stiffness also changes the electrical geometry, so rerun the affected field check on the manufactured arrangement.
References
- IEC/IEEE, IEC/IEEE 60076-57-129:2017, Power transformers – Part 57-129: Transformers for HVDC applications.
- CIGRE JWG A2/B4.28, Technical Brochure 406, HVDC Converter Transformers – Design review, test procedures, ageing evaluation and reliability in service, 2010.