Chenfan Electric
EN
Send drawing

ARTICLETechnical article

Commutation Failure: Reconstruct the Winding Currents

  • Chenfan Power

Commutation failure in an LCC bridge changes how current transfers between valves. The resulting transformer duty depends on the actual conducting combination and the event duration. A single missed transfer and repeated failures need separate current histories. Apply the HVDC transformer specification framework of IEC/IEEE 60076-57-129 to the stated liquid-immersed equipment [1].

Use the station transient model or recorded valve and phase currents. Label each conducting valve and the AC terminal it connects. Reconstruct phase currents with a consistent sign convention before referring them through the transformer vector connection.

Commutation Failure: Reconstruct the Winding Currents: technical review table
First article table, reproduced without adding or changing values. See the article for assumptions and application boundaries.

A conduction ledger that can be audited

Interval fieldPurpose
Start and end timesPreserve overlap and failed-transfer duration
Conducting valvesDefine the physical AC-to-DC current path
DC currentSet the current available in that path
Transformer phase currentsShow which winding sections carry current
Control and clearing stateExplain termination or repetition of the sequence

Do not infer that the intended firing pulse caused successful conduction. Voltage depression, overlap and valve recovery affect the actual transfer. The conducting-state record should agree with the calculated or measured phase currents.

Retain asymmetry as well as heating

For a simplified winding heating comparison, integrate ∫i²(t)dt for each phase over the complete event. The result has units A²s. Multiplication by a constant resistance in ohms yields joules, but real resistance and additional losses can vary with temperature and frequency.

Also retain current peaks and signed averages. Two histories can have a similar heating integral and different peak force or magnetic imbalance. Repeated failures can change the core’s initial state for the next interval, so concatenating identical isolated-event waveforms may be inadequate.

Compare equal heating with unequal current peaks

Assume rectangular phase-current screening histories of 2 kA for 0.10 s and 1 kA for 0.40 s, at the same initial temperature and constant winding resistance 0.010 Ω. Both give ∫i²dt = 400,000 A²s and resistive energy 4.0 kJ. Their peak-current ratio is 2, giving a force ratio of 4 only under unchanged linear geometry and current distribution. Thus equal heating does not clear the higher-peak case: retain both the current-squared integral and the synchronized force inputs.

State what the study actually covers

Specify the initiating AC disturbance, bridge group, control response, initial load and fault-clearing action. Check every winding using the multiwinding model; a line-current record on one terminal does not automatically reveal internal delta current.

Compare the time-indexed winding current with equipment data using separate heating, peak and asymmetry measures. Two sequences with equal heating integrals may impose different mechanical peaks. These measures do not yield a universal permissible count of commutation failures.

Include normal converter operation and converter-side faults in the transformer transient study [2].

References

  1. IEC/IEEE, IEC/IEEE 60076-57-129:2017, Power transformers – Part 57-129: Transformers for HVDC applications.
  2. CIGRE WG B4.51, Technical Brochure 609, Study of Converter Transients Imposed on the HVDC Converter Transformers, 2015.
Chenfan Electric

Direct coordination

Start a conversation.

A drawing, a material requirement, or a project to discuss.

Send drawing