Heating near a transformer core may arise in a conductive lamination path, a nearby clamp exposed to changing magnetic flux, or both. Heat can also travel from its source to the surface being viewed. The hottest visible pixel is therefore not automatically the location or type of electrical fault.
Start with two explicit hypotheses and the observations that would distinguish them. A test that can only confirm the presence of heat does not resolve whether the clamp or a lamination bridge produces it.

Locate source candidates in the same coordinates
Map the laminations, candidate contacts, clamp surfaces and thermal observation regions. Register time traces as well as image positions. Separate the physical heating of the clamp from reflected radiation off its surface, using a justified radiometric check. [1]
Draw the candidate conductive loop inside the laminations and identify the magnetic field that may drive currents in the clamp. These are different circuit boundaries. A current-related observation should be connected to the appropriate boundary rather than described only as an electrical signal near the core.
First: evaluate each path independently
For the lamination hypothesis, seek evidence for conductive connection, return path and relevant flux linkage. For the clamp hypothesis, characterize the actual conductive geometry and exposure to the changing field. Do not infer either mechanism solely from proximity to a joint.
Second: compare a justified boundary change
In a qualified research construction, change a relevant clamp boundary while preserving the packet condition as closely as possible. A change in heating may help discriminate the clamp mechanism. The trial must account for any simultaneous mechanical or cooling change introduced by the comparison.
This is not an instruction to remove or alter a structural clamp on a completed transformer. Such work requires design responsibility and an approved procedure. A purpose-built representative specimen can answer the research question without improvising on a deliverable assembly.
Third: compare transient patterns
Record when heating begins and how it spreads in each region. A clamp source warming a neighboring lamination has a different forward thermal problem from a lamination source warming the clamp. Test whether the measured patterns discriminate those alternatives under their actual boundary uncertainties.
Keep mixed outcomes visible
A comparison may reduce clamp heating while leaving a local lamination signal. That can support two contributors. Alternatively, the thermal map may change because the comparison changed contact cooling, while the electrical source remained similar.
Retain aggregate loss, local field or current evidence and thermal observations separately. Agreement among them strengthens a source attribution only when they represent the same state and location. Disagreement identifies a model or observation that needs refinement.
Assign the hotspot to a demonstrated current path or field-loss mechanism only after checking the competing explanation. If both remain plausible, retain both in the investigation and choose the next measurement to distinguish them.
Test a clamp-source hypothesis with heat capacity
Use catalogue 0.23 mm thickness and assumed density 7,650 kg/m³ [2]. Assume the observed core region contains 50 sheets, each 100 × 100 mm: mass is 0.87975 kg. With assumed specific heat 500 J/(kg·K), an initial 0.010 K/s slope corresponds to 4.399 W net heating if outflow is negligible. An assumed adjacent 1.00 kg clamp with the same specific heat and a 0.020 K/s slope corresponds to 10.0 W. The faster clamp rise supports investigating that source, but heat transfer between regions can invalidate both lumped estimates. Compare onset times and independent electrical evidence, with measurement and model uncertainty [3].
Manufacturing controls. Clamp geometry, joint leakage field, insulation between conductive structures, packet contact and duct cooling control the competing sources. Changing clamp restraint can change both magnetic exposure and heat flow, so retain both boundaries in comparisons.
References
- Deisenroth, D. C. et al., Measurement Uncertainty of Surface Temperature Distributions for Laser Powder Bed Fusion Processes, Journal of Research of NIST 126, 126013, 2021, sections 1.5 and 2.1; DOI: 10.6028/jres.126.013.
- Nippon Steel Corporation, Grain-Oriented Electrical Steel Sheets, catalogue D004je_03_202004, 2020, Specifications; Size and Form Tolerances.
- JCGM, JCGM 100:2008, Evaluation of measurement data — Guide to the expression of uncertainty in measurement, 2008.