Chenfan Electric
EN
Send drawing

ARTICLETechnical article

De-Embedding Transformer Test Leads: Move the Reference Plane with a Network

  • Chenfan Power

Move a transformer response to the winding-terminal reference plane through a characterized lead network. Include its series impedance, shunt admittance and return geometry, then remove them in the order defined by the connection topology.

Calculation basis. Unless a value is explicitly attributed to a cited source, numerical inputs in the demonstrations are assumptions for the stated model. Normalized variables are dimensionless. The examples define their own geometry, excitation and measurement boundary.

The decision is whether the lead network can be identified accurately enough to move the reference plane without amplifying measurement uncertainty beyond the useful signal.

Draw the two reference planes

Mark the instrument-side plane and the transformer-side plane on the connection drawing. Include the return conductor, tank connection and adapters in the identified external network. A lead length without its return geometry does not define a complete impedance.

Treat the lead and return arrangement as an electrical network. Its partial-path coefficients, complete-loop impedance and frequency dependence are different quantities; characterize the actual geometry and study band.

Calibration and de-embedding have related but distinct deliverables. Calibration establishes the instrument’s measurement plane under its stated procedure. De-embedding moves the response through an additional characterized network. Record where each operation acts so that the same cable segment is not removed twice.

Remove the characterized network in its physical order

For a two-port fixture, a chain representation can describe the cascade of input fixture, device and output fixture. With consistent voltage/current conventions, the device chain matrix is obtained by left and right inversion of the fixture matrices. That operation requires the matrices to be invertible and the fixtures to represent the actual connection.

A scalar transfer-function division is justified only by a topology in which the quantities genuinely multiply without unmodeled loading. A voltage detector changes the observed network through its input impedance. In a multiport transformer test, retain the unused-terminal conditions as well as the lead network.

Gustavsen and Heitz explicitly include external-network effects in their terminal-model accuracy analysis. A model should therefore be compared after connecting the external network appropriate to the measurement, or after that network has been removed through a documented transformation. [2]

Derive a transparent one-port example

Consider an original lead model consisting of a series inductance L_s = 5 µH, followed by a shunt capacitance C_p = 1 nF at the device plane. The device is a 100 Ω resistor, so Y_D = 0.010 S. The model is linear and lumped; it demonstrates the inversion and its sensitivity.

The measured input impedance is:

Z_m = jωL_s + 1/(Y_D + jωC_p).

Recovering the device admittance gives:

Y_D = 1/(Z_m − jωL_s) − jωC_p.

The order matters. Subtract the series impedance first, invert the remaining parallel impedance, then subtract the shunt admittance. Subtracting the capacitance directly from an impedance would also mix incompatible units.

At 1 MHz, the parallel branch is approximately 71.696 − j45.048 Ω and the measured input is 71.696 − j13.632 Ω. The correct inversion returns 10.000 mS with zero imaginary part. Subtracting the series lead alone would leave the shunt capacitance in the result.

At 10 MHz, the measured input is approximately 2.470 + j298.637 Ω. Its strongly inductive appearance is a property of the complete connection, even though the device itself remains the same resistor.

Instrument and device reference planes with series lead inductance, shunt capacitance, inverse calculation order and uncertainty at one and ten megahertz.
Original reference-plane and de-embedding calculation for a series-inductance/shunt-capacitance lead network. The operation order preserves the topology. The same 1 Ω local input error produces substantially greater recovered-admittance uncertainty at 10 MHz.

Quantify the inverse sensitivity

Let A = Z_m − jωL_s. For a small complex input-impedance error δZ_m, holding the lead parameters fixed, the first-order recovered-admittance error is:

δY_D ≈ −δZ_m/A².

Its magnitude is approximately |δZ_m|/|A|². A smaller residual impedance therefore increases uncertainty after inversion.

Constructed frequencyMagnitude of AApproximate admittance error for a 1 Ω complex input errorRelative to 10 mS
1 MHz84.673 Ω0.13948 mS1.395%
10 MHz15.718 Ω4.04784 mS40.478%

These are local derivative results, not simulated random noise or exact finite-error bounds. They show why a mathematically successful correction can still produce an unreliable recovered response. At 10 MHz, the transformation subtracts a large series term and then inverts a much smaller remainder.

Lead-parameter errors also propagate. For this topology:

δY_D ≈ −(δZ_m − jωδL_s)/A² − jωδC_p.

An inaccurate series inductance is amplified by the same inverse-square factor; a capacitance error grows directly with frequency. Characterizing the fixture and reporting only instrument uncertainty is therefore incomplete.

Use a closure test to decide the usable band

After de-embedding, reconnect the characterized lead network mathematically and compare the reconstructed input response with the measured input. This closure test catches sign, order, unit and reference-plane mistakes. It does not prove that an incorrect fixture model is physically right, so also check that the characterization matches the actual lead geometry.

Keep both raw and corrected complex data. Plot magnitude and phase, track the propagated uncertainty and flag frequencies where the inverse is dominated by subtraction or near-singularity. A correction that introduces rapidly growing conductance or an unexplained resonance should trigger a fixture and uncertainty review before a winding interpretation.

Hand over both reference planes, the lead model, characterization conditions, inversion method and accepted frequency range. Keep raw and recovered complex data together so the terminal response and propagated uncertainty can be reproduced.

Ruehli reconstructs closed-loop inductance from signed interactions between conductor segments. Retain the complete return path and current orientation before using a coefficient in the winding circuit. [1]

Gustavsen and Heitz show that fitted multiport accuracy depends on terminal conditions and the visibility of small modes. Validate the response used for the engineering decision under its actual terminal loads. [2]

References

[1] A. E. Ruehli, Inductance Calculations in a Complex Integrated Circuit Environment, 1972, DOI:10.1147/rd.165.0470.

[2] B. Gustavsen and C. Heitz, Modal Vector Fitting: A Tool for Generating Rational Models of High Accuracy with Arbitrary Terminal Conditions, 2008, DOI:10.1109/TADVP.2008.927810.

Chenfan Electric

Direct coordination

Start a conversation.

A drawing, a material requirement, or a project to discuss.

Send drawing