Chenfan Electric
EN
Send drawing

ARTICLETechnical article

Core Banding at Corners: Converting Strap Tension into Contact Pressure

  • Chenfan Power

Convert strap tension into local corner pressure using the actual contact radius and effective carrying width. Verify the strap–pad interface against that contact model, then retain the measured geometry and load path beside the tension setting.

Calculation basis. Numerical demonstrations use editorial assumptions unless a value is expressly attributed to a cited supplier, standard or published study. Dimensions describe the stated model geometry; test results introduced with “assume” or “suppose” are hypothetical inputs. Calculated outputs inherit those conditions.

Use a defined corner-contact model first, then verify the real contact and insulating pad. A nominal tension record cannot establish a peak pressure or a permissible indentation by itself.

Derive the local membrane estimate

Consider an ideal flexible, massless strap in full contact with a circular corner of radius r. Let its tension T be constant and its effective contact width be b. For a small angle dtheta, the inward resultant of the two tangent tensions is approximately T dtheta. The contact area is b r dtheta.

Equating local normal force and pressure times area gives p = T/(b r). More generally, the membrane relation follows local curvature rather than a whole-core projected area.

This estimate assumes negligible strap bending stiffness, uniform tension, full contact across the effective width and the stated contact contour. Model band bending, corner bridging and cushion compression explicitly when they affect contact. Friction or the closure device can also make tension differ around a real restraint.

For a flexible band with constant tension and negligible bending rigidity, balance a small arc element. The changing tension direction produces normal load per arc length T/r. Dividing by the engaged band width gives p = T/(br).

Keep radius and width in the tension record

For assumed T = 1000 N and b = 25 mm, a 10 mm radius gives p = 4.0 N/mm² = 4.0 MPa. With a 20 mm radius and the same assumed tension and width, the estimate is 2.0 MPa. Halving effective width would double either value within this model.

These calculations are illustrative. They are not measured pressures, approved tension settings or insulation strength limits. The radius must refer to the actual strap contact path. The bare steel corner radius may not describe the surface after adding a pad, and that pad can change shape as it is loaded.

A strap’s nominal width may also exceed its useful contact width. Rolled edges, a twisted strap, local core protrusions or pad extrusion can concentrate the load into less width. Record the contact evidence rather than assuming that every millimeter contributes equally.

Quarter-turn core-band contact sketch with a local pressure formula, two assumed radii and distinct vector and scalar reaction calculations.
An original quarter-turn strap sketch separates local membrane pressure from the vector corner reaction. Assumed tension, width and radii provide model calculations; no actual peak or pad limit is shown.

Distinguish scalar pressure load from a vector resultant

For constant model pressure on a quarter-circle contact, integrating the magnitudes of all normal contact forces gives T × pi/2. Their vector sum is different because the normal direction changes around the arc.

With equal tangent tensions T at a 90-degree turn, the resultant magnitude is sqrt(2) T. At the example’s T = 1000 N, that is about 1414 N, while the scalar integral is about 1571 N. Both follow the same ideal model; they answer different questions.

Dividing the vector resultant by the curved contact area would therefore give a different number from the local uniform model pressure. That quotient is not a replacement for p = T/(b r), nor does it locate a peak. Preserve the distinction when comparing a reaction-force output with a pressure plot.

Treat the computed pressure as a model quantity

The uniform circular membrane model has uniform p over its stated contact. A real corner may have local pressure peaks at pad edges, strap edges, wrinkles or transitions into straight faces. If the band bridges part of the contour, the assumed contact area is wrong before any material-strength comparison begins.

A sharp corner exposes the model’s limit: its pressure expression diverges as r approaches zero. Real band bending stiffness, local deformation and finite contact shape then matter. Reporting an infinite pressure is not a physical prediction, and silently inserting a convenient radius does not qualify the contact.

Use a resolved contact analysis where these effects drive the decision. State strap stiffness, corner/pad geometry, contact and friction assumptions, material behavior and the restrained assembly state. Check the model’s reactions and actual contact region as well as its displayed peak.

Verify the insulating pad at the local interface

Record pad identity, thickness, orientation, temperature and environmental condition. A short-duration compressive property at one material condition is not automatically a long-term indentation or dielectric limit for the assembled corner. The pad’s load spreading and electrical separation functions need their own evidence.

The development record combines a local contact observation with loaded and released pad-thickness or indentation observations. Inspect edge extrusion, cracking, permanent impressions and loss of the intended separation path. Use approved assembly and electrical verification methods rather than inventing one universal pressure threshold.

Select any pressure-indicating medium against the expected pressure, temperature, humidity and contact geometry. Check its thickness and stiffness because insertion can alter a small corner contact.

Release a corner-specific restraint definition

The handover should join strap tension evidence, effective width, contact contour, pad state, measured contact or validated model evidence, and the applicable mechanical and electrical criteria. If another strap material, pad or corner detail is substituted, review the local force path again.

Qualify the corner interface to carry the specified restraint while maintaining the pad’s mechanical and electrical function. Use its verified tension, contact contour and effective width as the assembly control for that design.

Use the sheet build to review corner-radius sensitivity

Nippon Steel lists 23ZH90 at a nominal steel thickness of 0.23 mm and an assumed density of 7.65 kg/dm³. [1] Assume a 100-sheet corner build, using only the 23.00 mm nominal steel contribution, around an assumed 10 mm inner radius. An ideal band acting at the resulting 33 mm outer radius, with T = 1,000 N and b = 25 mm, gives p = T/(br) = 1.212 MPa. Applying the 10 mm inner radius instead would predict 4.000 MPa, 3.30 times higher. Define the actual band-contact radius before using the membrane relation.

Manufacturing controls. Control layer build, band centreline, pad thickness, contact width, edge finish and band tension. Local seating and layer contact require their own check beyond the membrane average. [2]

References

[1] Nippon Steel Corporation, Grain-Oriented Electrical Steel Sheets, undated, specification tables and annealing compatibility.

[2] M. Pirnat, G. Čepon and M. Boltežar, Introduction of the linear contact model in the dynamic model of laminated structure dynamics: an experimental and numerical identification, 2013, DOI 10.1016/j.mechmachtheory.2013.02.003.

Chenfan Electric

Direct coordination

Start a conversation.

A drawing, a material requirement, or a project to discuss.

Send drawing