Eddy-Current Tube Inspection: Separate Defects from Supports

  • Chenfan Power
Eddy-Current Tube Inspection: Separate Defects from Supports: technical review table
First article table, reproduced without adding or changing values. See the article for assumptions and application boundaries.

Eddy-current signals from a cooler tube can reflect flaws, probe coupling, dents, magnetic deposits or supports. The IAEA tube-testing manual explains how these responses differ with frequency and geometry [1]. Use a matched reference piece and a component-specific procedure before classifying a support-region indication.

Identify alloy, diameter, wall, construction and access. Conventional eddy-current assumptions suitable for one nonferromagnetic tube do not automatically fit another material or a double-wall assembly. Select and qualify the technique for that construction.

Use a location-aware signal ledger

Signal classReference neededInterpretive limit
Known artificial featureMaterial/dimension-matched referenceCalibration response does not reproduce every real defect
Support regionActual support location and geometryGeometry response may mask degradation
Tube end/jointProbe travel and end arrangementCoverage can be limited
Unclassified indicationRepeat scan and complementary evidenceDo not assign unique cause from amplitude alone

Check what the probe can and cannot see

Record inspection speed, probe type, frequencies and the coverage actually achieved. Define which walls or surfaces the method is sensitive to in a double-tube cooler. The second wall and interspace can alter the response; a single-wall reference is not automatically adequate.

Separate signal detection from sizing and acceptance. A feature may be detected without its depth being reliably estimated. Conversely, a low signal can reflect unfavorable geometry or access rather than an intact wall.

ISO 20890-5 defines mechanised bore-side testing for non-ferromagnetic steam-generator tubes [2]. That defined scope does not qualify another alloy, a magnetic tube or a second wall in a transformer cooler. State which wall and flaw orientations the cooler procedure actually demonstrates.

Quantify the support-related blind lengths

Assume 20 tubes, each 3 m long, with two non-overlapping support intervals per tube. Each interval has 0.10 m axial length for which the required flaw sensitivity remains unproved. Unresolved length is 20 × 2 × 0.10 = 4 m out of 60 m, or 6.67%. This is an axial coverage inventory, not circumferential coverage or detection probability. Retain those intervals for a qualified complementary examination before closing the inspection scope.

References

  1. International Atomic Energy Agency, Eddy Current Testing at Level 2, Training Course Series 48, 2011, sections 5.2.2 and 6.3.
  2. ISO, ISO 20890-5:2020, Guidelines for in-service inspections for primary coolant circuit components of light water reactors — Part 5: Eddy current testing of steam generator heating tubes.