Compare surge-capacitor locations as different circuit nodes. Popov’s cable/no-cable measurements show propagation’s influence [1], while Rao and Gajjar model capacitive and suppression branches [2]. The placement analysis below is an application framework, not a published validation of this feeder.
Location is part of the transient model, not merely an installation label.

Compare the local wave boundaries
For a simple cable interface, voltage reflection coefficient is Γ = (Zload − Zcable)/(Zload + Zcable), using the relevant impedances at the frequency of interest. Adding a capacitor changes Zload through its shunt admittance at that location.
Transformer termination is generally frequency-dependent. Treating it as a fixed open circuit across the full band can distort the placement comparison.
| Candidate location | Wave relationship to retain | Assessment output |
|---|---|---|
| Transformer terminal | Acts at the arriving-wave boundary | Terminal slope, peak and component duty |
| Intermediate feeder node | Creates an additional reflection point | Arrival sequence at the transformer |
| Source-side node | Changes source loading and launched waves | Source/gap behavior and delayed terminal response |
Follow reflections through the complete event
Retain cable length, propagation and both terminal conditions. A reflected wave can return to the breaker while its gap is still recovering and influence later reignition. The capacitor’s effect therefore includes possible changes to the initiating sequence. [1]
Compare the same supported breaker characterization across placements. An ideal opening switch can conceal a placement-dependent change in reignition behavior.
At a local capacitor, current and voltage slope satisfy i = C dv/dt in the ideal component model. This explains one local slope effect, but the current itself changes when the network changes. It does not prove that adding capacitance will reduce every terminal peak by a fixed ratio.
Check the new circuit modes and duties
The added capacitor interacts with cable and transformer inductive behavior. Examine the resulting response bands and damping, not only the first reduced peak. A later oscillatory train can remain relevant to insulation or protective-component exposure. [2]
Retain normal-frequency burden, capacitor voltage, transient current and any arrester energy change. If placement reduces one terminal metric but increases another required duty, the comparison must show both.
Select the capacitor location from the complete switching cases, with the same supported breaker model in each comparison. Credit its effect through the validated wave path to the transformer, and retain the resulting capacitor, arrester and terminal duties in the selected arrangement.