Cathodic Disbondment on Buried Transformer Ancillary Steelwork

  • Chenfan Power

Buried ancillary steelwork can combine a coating with cathodic protection. At a coating defect, the exposed metal and nearby coating interface experience an electrochemical condition set by the protection system and electrolyte. The coating assessment should represent that boundary. [1]

ISO 15711 addresses sea-water exposure; a buried component needs a separately justified electrolyte and protection boundary for its actual soil service. [1] First confirm that cathodic protection actually applies to the component. An above-ground tank without that system should not inherit a buried-structure test conclusion merely because both are steel near a transformer.

Cathodic Disbondment on Buried Transformer Ancillary Steelwork: technical review table
First article table, reproduced without adding or changing values. See the article for assumptions and application boundaries.

Define the defect environment

BoundaryEvidence to specifyWhy it matters
Electrical conditionRelevant potential/reference and operating historyDefines the applied cathodic exposure
ElectrolyteSoil or test liquid conditionsControls the local electrochemical environment
Coating defectSize, shape and preparationSets exposed-metal/interface geometry
Coating systemMaterial, cure and substrate preparationDefines the adhesion/barrier premise

Inspect the interface after a defined exposure

Use the applicable qualified test to assess loss of adhesion around the defect. Retain the method for determining the affected boundary and its uncertainty. The result should distinguish damaged coating area from the intentionally exposed defect.

A laboratory condition can be deliberately severe, but that severity needs a stated relation to the service environment. No numerical life prediction follows from exposure time alone.

Keep paint execution and supervision tied to the actual product and coated region; a finished appearance does not recover missing process evidence. [2]

Separate the intentional defect from disbondment

Assumptions under one declared accelerated-test condition: a circular intentional defect is 5 mm diameter and the affected outer diameter is 15 mm. Excluding the intentional opening, annular affected area is π(15² − 5²)/4 = 157.1 mm². The defined radial advance from its edge is (15 − 5)/2 = 5 mm. Against an assumed project radial-advance criterion of at most 4 mm, it fails by 1 mm. Reject that specimen under the specified exposure and evaluate the protection/coating interface. Preserve the actual potential/reference, electrolyte, temperature and duration; neither this geometric result nor the sea-water method title establishes buried field life. [1]

References

  1. ISO, ISO 15711:2003, Paints and varnishes — Determination of resistance to cathodic disbonding of coatings exposed to sea water.
  2. ISO, ISO 12944-7:2017, Paints and varnishes — Corrosion protection of steel structures by protective paint systems — Part 7: Execution and supervision of paint work.