An underground-cable expansion adds earth capacitance and changes the compensation and detection duties. Update the electrical inventory, bus states and measurement model before accepting the existing Petersen-coil range for the expanded network. [1] [2]
Identify which cable sections become electrically connected in each operating state. Installed length, cable construction, sheath grounding and associated equipment all matter to the capacitance and measurement boundary.

Build the new capacitance inventory on a declared basis
For a cable section with capacitance per unit length c in farads per metre and installed length ℓ in metres, its corresponding capacitance is cℓ in farads. State whether c is per phase or already an aggregate value. If equal per-phase values are used for all three phases in a lumped model, their aggregate contribution is three times the per-phase result.
Add accessories, connected bus equipment and other relevant earth capacitance separately where they are not included in the cable data. Preserve installed-data uncertainty; a catalogue value and a measured installed response are different evidence.
| Before/after item | Evidence to update | Result affected |
|---|---|---|
| Connected cable inventory | Length, construction and capacitance basis | Capacitive-current envelope |
| Compensation branches | Available coils, connection impedance and calibration | Reachable effective range |
| Neutral-voltage response | New curve or suitable identification evidence | Tuning parameter confidence |
| Protection measurements | Residual phasors across updated states | Detection and directional coverage |
Compare effective range with the expanded state envelope
At a common stated voltage and angular frequency, the elementary aggregate capacitive current is IC = ωCΣU. Angular frequency is in radians per second, capacitance in farads and voltage in volts, giving amperes. Include relevant grounding-transformer impedance when deriving the actual compensation available from a coil branch.
For an illustrative planning comparison, an old maximum capacitive-current requirement of 120 A and an effective coil limit of 150 A leave 30 A of upper-range headroom. If the revised maximum is 160 A under the same basis, the gap is 10 A beyond that limit. The assumed values show how to report a gap; they are not installed equipment data.
Check minimum states as well as the expanded maximum. A coil arrangement can have adequate upper range while overcompensating a small remaining island because its minimum effective contribution is too large.
Update detection evidence with the new capacitance
Changed feeder charging currents can alter residual-current magnitude and angle, natural unbalance and observability. A protection characteristic assessed for the old feeder envelope may need new fault and nonfault evidence. Retain distributed compensation points and sensor locations in that update.
Reconcile the cable inventory with installed measurements, then check the reachable compensation and detection range for each relevant topology. Assign and resolve any range or observation gaps before the expanded network enters its intended operating state.
References
- A. Eberle GmbH & Co. KG, The Petersen-Coil Regulator, REG-DP/REG-DPA, including Current Injection and High Power Current Injection, Operating Instructions, April 2017.
- Q. Yang, B. Zhang, J. Ran, S. Chen, Y. He and J. Sun, Measurement of Line-to-Ground Capacitance in Distribution Network Considering Magnetizing Impedance’s Frequency Characteristic, Energies 10, 2017. DOI: 10.3390/en10040477.