Electrical-degree resolution becomes a power step through the connected network. Map discrete taps against voltage, impedance and topology to connect procurement’s angular data with the control study’s flow response. [1]
Calculation basis. Project-specific values and gates in the illustrative screens below are assumptions; cited catalogue values retain their source test conditions.

Write the sensitivity with its sign convention
In a restricted lossless two-bus model, define positive power from S to R and a positive device angle α that retards the sending-side effective voltage. Then P = K sin β, where β = θS − θR − α and K = VSVR/X with compatible bases. Holding bus angles and voltage magnitudes fixed gives dP/dα = −K cos β per radian. A per-degree sensitivity includes the factor π/180.
These definitions matter: changing the software or manufacturer’s angle convention can change the apparent sign. The derivative also assumes fixed bus conditions; a meshed-network solution generally allows those conditions to change.
Compare finite steps at different operating angles
For an illustrative K of 1,000 MW and a positive one-degree change in α, the effective angle β decreases by one degree. The exact finite-step response is ΔP = K[sin(β − 1°) − sin β].
| Assumed starting effective angle | Exact one-degree power change | Local derivative estimate |
|---|---|---|
| 0 degrees | −17.45 MW | −17.45 MW |
| 60 degrees | −8.86 MW | −8.73 MW |
The same electrical-degree step gives substantially different power changes. The small discrepancy between exact and derivative values at 60 degrees is the finite-step effect, not a calculation error. These operating angles are mathematical comparison cases, not a recommended device range or a statement about stable system operation.
Specify the response map that the controller needs
Obtain the actual no-load angle and ratio for each permitted tap or switch state, including unequal steps where present. Then solve representative network states to obtain the resulting branch-power changes. Include relevant outages, voltage conditions and reverse-transfer cases. A fixed-angle table alone cannot capture the redistribution among parallel paths.
Assess whether adjacent achievable states bracket the required flow target while satisfying internal current, terminal-voltage and system limits. Very fine angular resolution may provide little useful control in a low-sensitivity state; a larger power response may make a particular target impossible to hold without cycling between taps.
Specify angular data and agreed network cases in procurement. Use their response map to define the power effect of discrete states for the intended control study.
Translate one tap into a power-flow step
Tie the model and acceptance evidence to the specific PST application and tested configuration [2].
Assume a lossless equal-voltage branch on a 100 MVA base with X = 0.20 per unit, angle δ = 10° and a 1° phase-shift step opposing δ. P = sinδ/X changes from 0.86824 to 0.78217 per unit, or from 86.82 MW to 78.22 MW. The 8.61 MW step is an operating-point result; recompute it across the actual network states.
References
- B. Cook, M. J. Thompson, K. Garg and M. Malichkar, Phase-Shifting Transformer Control and Protection Settings Verification, 2018. DOI: 10.1109/CPRE.2018.8349815.
- IEC, IEC 62032:2012, Guide for the Application, Specification and Testing of Phase-Shifting Transformers.