Multiwinding Harmonic Loss: Preserve Phase and Integrate by Physical Region

  • Chenfan Power

Preserve synchronized current phase in a multiwinding harmonic-loss calculation. Fields from the windings combine at each frequency before regional dissipation is calculated, creating cross terms that change both total power and its allocation.

A useful allocation identifies the physical conductor regions where power is dissipated. It does not assign every interaction term to the winding whose terminal current happens to be largest.

Define the harmonic current coordinates consistently

For each frequency, retain a complex RMS current vector, its terminal polarity references and the actual connection constraints. Phases must refer to a common time origin. Independently measured spectra need sufficient synchronization to establish those relative phases.

Include the connections that constrain a multiwinding transformer. A floating winding, grounded terminal or parallel connection changes the permitted currents and induced response. The independent current coordinates used in a reduced model need not correspond one-to-one with its physical loss regions.

Do not choose arbitrary phase combinations as though they were all feasible operating points. The winding circuit, excitation and loads determine the actual current vector. A mathematical sensitivity case illustrates an effect, rather than qualifying an equipment duty.

Keep interactions within each frequency

Use a frequency-dependent quadratic resistance representation for a linear connected winding model. Retain complex RMS current phasors so interactions between currents at the same frequency remain in the power calculation.

Measured impedance can include core and capacitive effects. Extract the represented winding dissipation using a documented field or circuit model before assigning it to a physical conductor region.

For a linear field response at a fixed material state, the current density in a physical conductor region can be written as a sum of unit-excitation responses. If g_m is the region’s current-density response to current coordinate m, then J = Σ g_m I_m.

Integrating |J|²/σ for ordinary real conductivity produces a regional quadratic form:

P_k,n = I_n† H_k,n I_n

Here k identifies a physical loss region, n a harmonic, and † denotes conjugate transpose. H_k,n is the Hermitian regional dissipation matrix obtained by expanding the stated current-density integral under the RMS convention.

Allocate by region before summing the equipment boundary

The off-diagonal terms arise because fields from different excitations overlap within the same region. Their sign can depend on relative phase. A negative cross contribution does not mean that a passive conductor generates negative heat; the complete regional quadratic form must remain nonnegative.

Integrate each physical region once. Sum the regional matrices to obtain the matrix over their combined loss boundary. If structural conductors or connection regions are excluded, a sum over winding regions alone is not the complete equipment loss.

Avoid separately adding a circulating-current loss estimate to a current-density solution that already contains those currents. Define the field components and circuit constraints represented by the calculation so its regional totals remain traceable.

Evaluate an hypothetical regional matrix example

Consider two independent RMS current coordinates in a deliberately abstract linear multiwinding model. Assume that other terminal constraints have already been incorporated. Its three physical winding-conductor regions are A, B and C.

Assumption: Assign the following assumed real symmetric matrices, in milliohms:

RegionH₁₁H₂₂H₁₂ = H₂₁
Winding region A1.01.0+0.5
Winding region B0.60.8−0.2
Winding region C0.20.4+0.1
Combined three-region boundary1.82.2+0.4

These matrices are positive definite. They are chosen to demonstrate a consistent quadratic ledger, rather than extracted from an impedance test or computed field solution.

At an assumed 50 Hz component, set the two coordinate currents to 100 A and 80 A with relative phase φ. For each region, the cross contribution is 2H₁₂ × 100 × 80 × cosφ, with milliohms converted to ohms.

Relative phase φRegion ARegion BRegion CThree-region total
0°24.40 W7.92 W6.16 W38.48 W
90°16.40 W11.12 W4.56 W32.08 W
180°8.40 W14.32 W2.96 W25.68 W

The current magnitudes are unchanged, yet the regional losses change. At 180°, region B has more dissipation than at 0°, even though the three-region total is lower. Neither the lower total nor a regional power predicts a hotspot temperature without the spatial heat source and thermal conditions.

Invented positive-definite matrices for three winding regions and a one-harmonic phase table show individual losses and a consistent total for two reduced RMS current coordinates.
The original fictional matrix example retains same-frequency current phase and sums three non-overlapping conductor regions. It demonstrates allocation and arithmetic consistency, without claiming a feasible equipment operating point or measured winding losses.

Sum harmonics only within a valid linear framework

For a periodic linear response with fixed material properties, distinct harmonic terms can be summed after their separate regional powers are evaluated. Integrate over a complete relevant period so cross-frequency products average as required. Preserve phase interactions between windings at each individual harmonic.

If the field response, conductivity or magnetic state changes with excitation, assess the applicable nonlinear or operating-point model. A fixed resistance matrix cannot establish unrestricted harmonic superposition in that situation.

Report DC contributions separately where relevant. Also preserve the frequency dependence of each matrix: a matrix determined at the fundamental frequency cannot automatically describe every higher harmonic.

Make the allocation reproducible

Retain synchronized current phasors, terminal references, connection constraints, material state and the extraction or field basis for every regional matrix. Reconcile the sum of regional powers with the combined quadratic form using the same current vector.

Then compare the complete modeled loss boundary with the applicable power balance and physical validation evidence. The hypothetical example closes its own regional arithmetic, but supplies neither actual source feasibility nor a validated transformer model.

Allocate dissipation by physical region and reconcile the matrix sum using the same current vector. Retain phase, connection constraints and the represented loss boundary so the winding decision follows where heat is generated.

The transformer loss boundary includes winding resistance heating. [1] For a measured comparison, retain the uncertainty and any shared error contributions with the reported difference. [2]

References

[1] U.S. Bureau of Reclamation, Transformers: Basics, Maintenance, and Diagnostics, April 2005, Sections 2.6 and 2.9.

[2] Barry N. Taylor and Chris E. Kuyatt, NIST Technical Note 1297, Guidelines for Evaluating and Expressing the Uncertainty of NIST Measurement Results, 1994.