Include the lead exit, bracket and terminal in the fault load path. Their connected geometry and relative restraint determine both local electromagnetic demand and the displacement outside the final winding turn.
Include the conductor outside the winding body
The local electromagnetic load follows the conductor current and magnetic field. Lead bends, adjacent phase conductors and return paths change the direction and distribution of force. Retain the complete connected conductor geometry where it controls the local response.
Mechanical restraint is equally specific. A winding exit, a clamp and a tank-mounted terminal can move relative to one another. A fixed support placed at the wrong location transfers the load through a stiffness that the assembly does not possess.
Calculate a transparent load example
Assumption: For two long parallel conductors in a nonmagnetic medium, force per unit length has magnitude q = μ0I1I2/(2πd). Choose simultaneous currents of 10 kA in each conductor and separation d = 50 mm. The idealized force magnitude is 400 N/m; its direction depends on the current directions.
Apply that uniform transverse load to a selected 0.20 m cantilever lead segment. Total load is 80 N and root moment is qL²/2 = 8 N·m.
With selected bending rigidity EI = 100 N·m², tip displacement is qL⁴/(8EI) = 0.8 mm. At EI = 10 N·m², displacement becomes 8 mm. Load and root moment are unchanged.

This example separates electromagnetic demand from mechanical response. A satisfactory force calculation does not establish clearance retention; the connected stiffness determines displacement.
Resolve bends and attachments
Use the local vector load for a curved or angled exit. The long-parallel-conductor expression supplies a defined comparison, not the field distribution around every lead bend. Include conductor cross-section, insulation support and bracket geometry in the structural representation.
At an attachment, distinguish the conductor load from the fastener, weld or clamp demand. Frictional restraint, compression contact and bonded restraint carry different force components. The support definition must match the joint being assessed.
Report the quantities that drive the decision
Identify lead displacement relative to neighboring live parts and grounded structures, conductor strain at the bend, and reaction loads entering the bracket and terminal. Evaluate them at the same time in the fault response rather than combining unrelated maxima into an impossible state.
Use the calculated load path to select span length, bracket position and bending rigidity. Carry the resulting reactions into the attachment design and check the changed lead clearance in the same fault state.
IEC 60076-5 addresses thermal and dynamic withstand of external short circuits. The support model and its validation should resolve the mechanical quantity used in that assessment. [1]
Carry uncertainty in the measured model inputs and responses into the comparison, including correlated contributions. [2]
References
[1] IEC, IEC 60076-5:2006, Power transformers — Part 5: Ability to withstand short circuit.
[2] Barry N. Taylor and Chris E. Kuyatt, NIST Technical Note 1297, Guidelines for Evaluating and Expressing the Uncertainty of NIST Measurement Results, 1994.