Chenfan Electric
Français
Envoyer un plan
Retour aux vidéos techniques

Bibliothèque de vidéos techniques

Capitalizing Transformer Losses in Total Ownership Cost

Durée 00:56 · 1920 × 1080

Présentation technique

Transformer loss capitalization converts stated loss differences into evaluated cost. This video connects core and load losses with the agreed economic assumptions and operating profile. The purchase-price comparison needs the same evaluation basis for every offered design.

Télécharger les sous-titres

Transcription
The cheapest core may not give the lowest evaluated cost. The article uses total cost of ownership: purchase price, plus capitalized no-load loss and load loss. Its example assumes continuous annual energization, electricity at ten cents per kilowatt-hour, thirty years of service, and an eight percent discount rate. The stated present-value factor is eleven point two six. That gives about nine dollars ninety per watt of no-load loss. Under those assumptions, one hundred watts less is worth about nine hundred ninety dollars today. These are calculated values, not measured savings or a utility tariff. Use your own energy price, operating schedule and evaluation factors. Compare guaranteed losses and verify production results.

Demande de renseignements sur un projet

Contacter notre équipe ↗
Chenfan Electric

Coordination directe

Parlons de votre projet.

Un plan, un besoin en matériau ou un projet à étudier.

Envoyer un plan