Capitalizing Transformer Losses in Total Ownership Cost

Длительность 00:56 · 1920 × 1080

Техническое описание

Transformer loss capitalization converts stated loss differences into evaluated cost. This video connects core and load losses with the agreed economic assumptions and operating profile. The purchase-price comparison needs the same evaluation basis for every offered design.

Скачать субтитры

Текстовая расшифровка
The cheapest core may not give the lowest evaluated cost. The article uses total cost of ownership: purchase price, plus capitalized no-load loss and load loss. Its example assumes continuous annual energization, electricity at ten cents per kilowatt-hour, thirty years of service, and an eight percent discount rate. The stated present-value factor is eleven point two six. That gives about nine dollars ninety per watt of no-load loss. Under those assumptions, one hundred watts less is worth about nine hundred ninety dollars today. These are calculated values, not measured savings or a utility tariff. Use your own energy price, operating schedule and evaluation factors. Compare guaranteed losses and verify production results.