WEBVTT 00:00:00.452 --> 00:00:01.974 The cheapest core may not give 00:00:01.989 --> 00:00:03.793 the lowest evaluated cost. 00:00:04.660 --> 00:00:06.455 The article uses total cost of 00:00:06.470 --> 00:00:07.025 ownership: 00:00:07.108 --> 00:00:09.450 purchase price, plus capitalized no-load 00:00:09.465 --> 00:00:10.592 loss and load loss. 00:00:11.457 --> 00:00:13.603 Its example assumes continuous annual 00:00:13.618 --> 00:00:16.038 energization, electricity at ten cents per 00:00:16.053 --> 00:00:18.053 kilowatt-hour, thirty years of service, 00:00:18.189 --> 00:00:19.876 and an eight percent discount rate. 00:00:20.728 --> 00:00:23.148 The stated present-value factor is eleven 00:00:23.163 --> 00:00:24.186 point two six. 00:00:25.051 --> 00:00:26.989 That gives about nine dollars ninety 00:00:27.004 --> 00:00:28.470 per watt of no-load loss. 00:00:29.321 --> 00:00:30.514 Under those assumptions, 00:00:30.636 --> 00:00:32.119 one hundred watts less is worth 00:00:32.134 --> 00:00:34.303 about nine hundred ninety dollars today. 00:00:35.168 --> 00:00:36.855 These are calculated values, 00:00:36.965 --> 00:00:38.903 not measured savings or a utility 00:00:38.918 --> 00:00:39.486 tariff. 00:00:40.350 --> 00:00:41.907 Use your own energy price, 00:00:42.069 --> 00:00:44.694 operating schedule and evaluation factors. 00:00:45.545 --> 00:00:47.705 Compare guaranteed losses and verify 00:00:47.720 --> 00:00:48.939 production results.