Define the foil junctions before calculating current sharing. Electrically parallel layers require separate branch currents; series turns carry the same net circuit current even when their local current-density distributions differ.
For a winding that does use parallel layers, the attachment geometry is part of the electrical path. Equal foil thickness and a common external terminal do not establish equal branch impedance or equal linked flux around the loops formed by those paths.
Draw the electrical connections before simplifying the winding
Identify which layers join at each end, their polarity and effective turns. Retain the length and location of the attachment from each layer to the common junction. A shared terminal label can conceal different routes between the foil and that junction.
Include the physical start and return route of every parallel path. End connections close magnetic contours and can add linked flux outside the winding body.
For a power-frequency winding, retain the actual attachment geometry when deriving the coupled branch parameters.
Retain mutual coupling in the branch model
A reduced circuit should distinguish each path’s resistance from its self and mutual inductive terms. A pair of independent scalar impedances may lose the coupled field interaction that determines current sharing.
For an illustrative linear two-path model, let the branch resistance values be R1 and R2, self-inductances L1 and L2, and mutual inductance M. Use a consistent winding polarity and sinusoidal RMS phasors. Assume the externally induced voltage contribution is identical in the two paths, so it cancels when their voltage equations are subtracted.
Let U denote the terminal voltage after subtracting that common external induced contribution. The two reduced path equations are:
U1 = (R1 + jωL1)I1 + jωMI2
U2 = jωMI1 + (R2 + jωL2)I2
With U1 = U2 and I1 + I2 = I_total, subtraction gives:
[R1 + jω(L1 − M)]I1 = [R2 + jω(L2 − M)]I2
Use this reduced relation when the branches share the stated induced voltage and the diagonal resistance model represents their loss. Otherwise retain differential excitation and the full impedance matrix.
Solve a declared power-frequency example
Assumption: Assume f = 50 Hz, R1 = 1.00 mΩ, R2 = 1.20 mΩ, L1 = 20 μH, L2 = 24 μH and M = 18 μH. Prescribe the total current phasor as 1,000 + j0 A RMS. These are original hypothetical circuit values, not measured transformer parameters.
The two reduced impedance terms are approximately 1.000 + j0.6283 mΩ and 1.200 + j1.8850 mΩ. Solving their ratio with the total-current constraint gives:
| Hypothetical branch | Current phasor, A RMS | Current magnitude | Represented resistor dissipation |
|---|---|---|---|
| Path 1 | 661.26 + j101.37 | 668.99 A | 447.55 W |
| Path 2 | 338.74 − j101.37 | 353.58 A | 150.02 W |
The phasors sum to the prescribed total. Their magnitudes do not sum to 1,000 A because their phases differ. Splitting the total into two assumed 500 A magnitudes would miss that result.
The listed dissipation is Rk|Ik|² for the resistors represented in this circuit. It is not a complete spatial winding-loss calculation. Skin, proximity and contact-spreading losses require their corresponding spatial conductor models.

Distinguish branch imbalance from local current concentration
A branch current is an integral over its conducting cross-section. It does not describe how the current is distributed across a wide foil, around an attachment edge or through a joint. A branch with a moderate net current can still have a locally concentrated current density.
A hotspot assessment therefore needs the applicable spatial conductor-loss and thermal representation. For ordinary local resistive heating, the current-density distribution and conductivity determine the local heat source; cooling and contact conditions then affect temperature. A pair of total branch currents cannot supply those spatial quantities.
Likewise, a measured whole-winding resistance does not isolate which terminal or foil region generates the loss. A useful comparison should retain the region boundaries used for conductor and attachment losses, together with their connection to the thermal model or measurement.
State the frequency and geometry behind the model
A series layer and a parallel layer have different current constraints. Resolve their actual terminals before importing any conductor approximation that omits edge or end effects.
At 50 Hz, solve the declared circuit with its own parameters and its complete end-connection geometry.
Where the actual end geometry is important, an appropriate field-circuit model must retain it or justify the equivalent parameters used in its place. Preserve the represented frequency, material state, connection resistance and coupling basis. Changing terminal routes after parameter extraction changes the configuration being assessed.
Make the comparison reproducible
The completed review should connect the electrical topology, physical terminal paths, applicable impedance description and branch-current result. Then distinguish the represented branch losses from the additional spatial and thermal evidence needed for hotspots.
Identify the junctions, retain their mutual coupling and solve the actual branch currents. Use the represented resistor losses for the circuit comparison, then connect the local conductor and attachment losses to the hotspot assessment.
The transformer loss boundary includes winding resistance heating. [1] For a measured comparison, retain the uncertainty and any shared error contributions with the reported difference. [2]
References
[1] U.S. Bureau of Reclamation, Transformers: Basics, Maintenance, and Diagnostics, April 2005, Sections 2.6 and 2.9.
[2] Barry N. Taylor and Chris E. Kuyatt, NIST Technical Note 1297, Guidelines for Evaluating and Expressing the Uncertainty of NIST Measurement Results, 1994.