Rate-Dependent Hysteresis Models: Avoiding Double Counting of Dynamic Loss

  • Chenfan Power

Assign each dynamic-loss contribution one accounting owner. A finite-rate B–H model can already include the eddy energy that a separate postprocessor would add, so reconcile the equations and calibration boundary before totaling the outputs.

Calculation basis. Unless a value is explicitly attributed to a cited source, numerical inputs in the demonstrations are assumptions for the stated model. Normalized variables are dimensionless. The examples define their own geometry, excitation and measurement boundary.

Start the review with a mechanism ledger. Identify what the constitutive model, field solution and loss postprocessor each include, at the same spatial, waveform and averaging boundary. Names such as “hysteresis loss” or “core loss” are insufficient definitions.

Audit what the fitted loop contains

Record how the constitutive data were obtained and how they were fitted. A model identified from quasi-static trajectories aims to represent a different boundary from a model fitted to finite-rate loops that already contain dynamic broadening. Calling both models hysteretic does not make their loss outputs interchangeable.

Inspect every dynamic term embedded in the constitutive law and its energy balance. A finite-rate fitted loop may already contain the contribution that a separate eddy-loss postprocessor would add.

This provides a concrete warning: a dynamic constitutive formulation may incorporate mechanisms that another part of the workflow also computes. Read the actual equations and calibration definition before adding a correction. A frequency-dependent fitted coefficient can also absorb several effects without identifying them separately.

Assign one owner to each included mechanism

Prepare a ledger for each modeled region. State the physical mechanism, mathematical representation, source of its parameters, energy or power units, and where the result enters the total. If a contribution has two owners, establish whether they describe distinct effects or overlapping representations of the same effect.

RepresentationWhat must be establishedPotential overlap
Quasi-static hysteretic constitutive responseWhich rate effects remain in its calibrationA fitted loss coefficient may include residual dynamic effects
Dynamic hysteretic constitutive responseWhich dynamic terms are embedded in its equationsAn added classical or excess term may duplicate embedded energy
Conductive field solutionWhich currents and regions are explicitly resolvedA separate lamination correction may represent the same currents
Empirical total-loss postprocessorWhich mechanisms its calibration totals includeAdding a solver subtotal to an already complete empirical total

Compare the definitions in the actual implementation. A resolved macroscopic conductor current and a modeled unresolved microscopic contribution can coexist when their physical and mathematical boundaries are complementary.

Read each loss-output definition in the actual field and constitutive equations. Keep a resistive-heating subtotal separate from an empirical total that may already include it.

Keep loop energy and average power separate

For a closed scalar magnetic cycle under the appropriate constitutive boundary, the integral of H dB is an energy density, in J/m³. Average power density for an identical repeated cycle is that energy divided by the period, or f times the energy. Do not compare an energy-per-cycle output directly with a power-density output.

A transient that ends in a different magnetic state also changes stored energy. It cannot be treated as a closed-loop dissipation solely by connecting its endpoints on a plot. In a coupled field model, inspect the applicable energy balance, the definition of the constitutive field and the solver’s conductive dissipation. A broad loop involving an effective dynamic field is not automatically a purely static hysteresis subtotal.

An original accounting counterexample

Suppose a hypothetical closed cycle at 50 Hz has assigned energy densities of 40 J/m³ for a quasi-static contribution, 12 J/m³ for a classical dynamic contribution and 8 J/m³ for another dynamic contribution. These are teaching allocations, not separated experimental measurements.

A complete dynamic model that includes all three gives 60 J/m³ per cycle and 3,000 W/m³. Adding the same 12 J/m³ classical contribution again gives 72 J/m³ and 3,600 W/m³. The apparent total is 20% too high solely because of duplicated bookkeeping.

Hypothetical complete dynamic cycle includes 40, 12 and 8 joules per cubic metre; adding the same 12 again makes the 50-hertz total twenty percent too high.
An original hypothetical energy ledger shows a classical contribution already included in the dynamic total. Adding it again creates a 20% error at 50 Hz. The rate rows are assigned arithmetic, not measured steel losses.

For an additional hypothetical rate check, define the classical cycle term as 0.24 f J/m³ when f is entered numerically in hertz, and the other dynamic cycle term as 8√(f/50) J/m³. Keep the quasi-static cycle term at 40 J/m³. These functions specify an arithmetic toy; they are not validated steel laws.

Repetition rateComplete cycle energyComplete average powerDuplicate classical energy if added again
25 Hz51.657 J/m³1,291.4 W/m³6 J/m³
50 Hz60.000 J/m³3,000.0 W/m³12 J/m³
100 Hz75.314 J/m³7,531.4 W/m³24 J/m³

The duplicated error changes with rate. A correction tuned to conceal it at one rate can therefore distort predictions at another. These calculations demonstrate accounting, not a procedure for experimentally separating losses into three terms.

Validate the implementation at more than one rate

Use measured trajectories appropriate to the actual material, direction, stress, temperature, flux range and waveform. Preserve the full ordered waveform. A changed frequency with a changed flux amplitude or waveform shape does not isolate a rate effect.

For each declared case, compare cycle energy, average power and the reconstructed magnetic response at matching boundaries. Keep at least one relevant rate or waveform outside coefficient fitting. Review time-step, mesh and numerical-integration sensitivity before attributing a mismatch to material physics.

Where a conductive field contribution is explicitly resolved, inspect its volume and current definition. Where laminations are homogenized, record which unresolved effects the constitutive or empirical model supplies. Do not subtract a vaguely named “eddy loss” from measured total loss and assume the remainder is uniquely quasi-static; the decomposition needs a justified model and uncertainty assessment.

Release an auditable total

The final result should name each included mechanism once, show its units and averaging period, and identify omissions. If two calculations cannot be shown to have complementary boundaries, keep their relationship unresolved instead of quietly adding them.

Check the mechanism ledger against independent rates and waveforms, alongside the measured total. That comparison exposes duplicated and omitted terms that can otherwise cancel at one calibration point, and leaves a total whose units and physical contents are traceable.

Reconcile the rate check with total catalog loss

For M-3X at 1.7 T, the catalog maxima are 0.453 W/lb at 50 Hz and 0.580 W/lb at 60 Hz. [1] These convert to 0.998694 and 1.278681 W/kg, an increase of 28.035%. Energy per cycle is 19.973881 and 21.311352 mJ/kg, respectively, an increase of 6.696%. A model’s power and loop-area checks must therefore retain their own frequency factors. The two catalog totals do not independently identify quasi-static, classical and excess components; validate a proposed decomposition against additional evidence.

Control grade, sheet thickness, cutting stress, joint overlap and interlaminar insulation. Keep manufacturing-related excess assembly loss separate from mechanisms already contained in a calibrated finite-rate material law. IEC 60404-8-7 provides the delivery-specification framework for fully processed grain-oriented steel. [2]