Identify CTC bending and interstrand shear independently. A strand pack can be stiff in longitudinal extension yet compliant in shear and bending; a long-span deflection fit mainly identifies bending and can leave the short-span fault response poorly represented.
Use independent bending and shear observables, then verify the equivalent model in the support arrangement used by the winding. The model should preserve how the pack transfers load, not merely its outer dimensions.
Strand coupling changes the section’s bending rigidity
For the stated linear beam model, bending rigidity is D = EI, with I measured about the bending neutral axis. The coupling question is which strands share that neutral-axis strain field.
Assumption: An ideal four-layer example makes the range clear. Each layer is 10 mm wide and 1 mm thick, with E = 100 GPa. If the layers slide freely, the bending rigidity is the sum of their individual centroidal rigidities:
D_free = 4Ebt³/12 = 0.3333 N·m².
If the same layers are perfectly bonded and act as a solid 4 mm section:
D_bonded = Eb(4t)³/12 = 5.3333 N·m².
The ratio is 16. The added rigidity comes from the distance of each layer from the shared neutral axis; it is not an increase in the metal’s longitudinal modulus. This idealized laminate is a coupling benchmark, not a geometric model of an actual transposed cable.
For CTC, strand transposition, insulation, bonding, contact pressure and relative slip determine how much of the shared-section behavior is developed. An effective modulus inferred from one bending test combines those mechanisms with the test’s span and restraints.
Separate bending compliance from shear compliance
For a linear cantilever model with end force F, bending rigidity D and effective shear rigidity S, the end displacement is:
δ = FL³/(3D) + FL/S.
The first term grows with the cube of span; the second grows linearly. S represents the effective shear-force to shear-strain relation, including the model’s shear correction convention. It should not be silently equated to a bulk-metal value.
Take D = 5.3333 N·m², S = 100 kN and F = 10 N. The independently calculated contributions are:
| Span, mm | Bending displacement, mm | Shear displacement, mm | Total, mm |
|---|---|---|---|
| 50 | 0.0781 | 0.0050 | 0.0831 |
| 100 | 0.6250 | 0.0100 | 0.6350 |
| 200 | 5.0000 | 0.0200 | 5.0200 |
At 50 mm, shear contributes 6.0% of the total displacement. At 200 mm, it contributes only 0.40%. A long-span fit can therefore match total movement closely while providing very little information about S. A model with the wrong shear rigidity may still look convincing in that test.

Choose tests that identify the parameters
Use a pure-moment or constant-moment region to obtain curvature and bending rigidity with minimal shear influence. Add shorter-span loading with measured displacement and section rotation to resolve shear deformation. Test both relevant bending directions because the strand layout and pack dimensions can create different rigidities.
When using several cantilever spans, fit δ/(FL) = L²/(3D) + 1/S. The slope identifies 1/(3D), while the intercept identifies 1/S. Fixture compliance can also contribute an apparent intercept. Measure or remove that compliance before interpreting it as strand-pack shear.
Maintain the conditioning and normal confinement expected in the winding. A freely supported specimen and a clamped conductor pack can mobilize different interstrand load transfer. Record any amplitude dependence or hysteresis. If the response changes with slip state, one constant orthotropic elastic tensor cannot represent the entire loading range.
Verify the equivalent model at the structural scale
After identifying the parameters, predict a loading arrangement that was not used in the fit: a different span, combined bending and shear, or the actual spacer-supported segment. Compare deflection, rotation and reactions. A match in only one scalar displacement is weak evidence because different parameter combinations can reproduce that number.
The release record should list longitudinal stiffness, the two bending rigidities, the relevant shear rigidities and their identified loading range. Where the model uses a continuum tensor, check that its predicted beam rigidities reproduce those measured quantities without double-counting section geometry.
Release a CTC equivalent model against several independent responses. Verify bending, shear and support reactions over the identified load range; use a single modulus where the governing analysis shows that shear and slip have negligible influence.
IEC 60076-5 addresses thermal and dynamic withstand of external short circuits. The support model and its validation should resolve the mechanical quantity used in that assessment. [1]
Carry uncertainty in the measured model inputs and responses into the comparison, including correlated contributions. [2]
References
[1] IEC, IEC 60076-5:2006, Power transformers — Part 5: Ability to withstand short circuit.
[2] Barry N. Taylor and Chris E. Kuyatt, NIST Technical Note 1297, Guidelines for Evaluating and Expressing the Uncertainty of NIST Measurement Results, 1994.