Study pole scatter and chopping as one event sequence. Each pole’s separation and interruption time sets its current, magnetic state and gap recovery, while phase coupling carries that state into subsequent reignitions. [1] [2]
Rao and Gajjar’s generic model identifies arcing time, chopping, recovery and high-frequency quenching as separate properties. A project study needs their supported relationship for the actual breaker and circuit.

Keep the physical event times distinct
Retain the common command, contact-separation times and effective electrical interruptions by phase. The interval between separation and the relevant current zero affects the gap state when recovery voltage appears. [2]
Declare source phase, phase sequence and the pre-event load/magnetic condition. A relative pole-delay set without an absolute waveform reference does not establish the interrupted currents.
Build a joint map rather than independent extremes
| Map input | Relationship to retain | Response to compare |
|---|---|---|
| Absolute separation time | Position on each phase waveform | Current and magnetic state |
| Relative pole delays | Intermediate three-phase topology | Coupled currents and recovery voltages |
| Current-chop behavior | Supported dependence and uncertainty | Initial energy redistribution |
| Recovery and quenching | Gap history and high-frequency current | Reignition sequence and final interruption |
Use correlated characterization where available. Rao and Gajjar use typical stochastic settings [2], not a measured joint distribution for this breaker. If only independent ranges exist, label their combinations as sensitivity cases and identify those not shown physically attainable.
Retain phase coupling through the event
The first interrupted phase can influence the remaining phases through high-frequency paths. A model with independent phase circuits cannot assess virtual chopping or phase-to-phase stress created by that sequence. [2]
Carry capacitor voltages and magnetic states through every pole event. Resetting the circuit after each phase interrupts removes the interaction being studied.
Compare phase-ground and phase-phase waveforms, breaker gap stress, event count and protective-component duty. The case with the largest terminal peak need not govern every other quantity.
Separate an envelope from probability
A set of simulated extremes can define an investigated envelope. It cannot establish how frequently those events occur without a supported statistical basis, sampling method and adequate coverage. [2]
Check numerical convergence and refine regions where small timing changes alter the sequence. Preserve unresolved combinations instead of selecting one visually severe trace as the complete result.
Identify the jointly credible event conditions governing each required stress. Obtain correlated breaker characterization where an extreme result depends on an unverified combination; retain that case as a conditional bound until it is resolved. Carry the event sequence and component duties into the final acceptance record.
References
- M. Popov, R. P. P. Smeets, L. van der Sluis, H. de Herdt and J. Declercq, Experimental and Theoretical Analysis of Vacuum Circuit Breaker Prestrike Effect on a Transformer, IEEE Transactions on Power Delivery 24, 2009. DOI: 10.1109/TPWRD.2009.2013383.
- B. Kondala Rao and G. Gajjar, Development and Application of Vacuum Circuit Breaker Model in Electromagnetic Transient Simulation, IEEE, 2006. DOI: 10.1109/POWERI.2006.1632503.