Chenfan Electric
EN
Send drawing

ARTICLETechnical article

Bayesian FRA Updating: Keep the Competing Winding Models Visible

  • Chenfan Power

Use Bayesian updating to retain the feasible winding explanations and their weights after a measurement. Combine an explicit engineering prior with the stated observation model, then inspect the competing posterior modes before choosing the next test.

Calculation basis. Unless a value is explicitly attributed to a cited source, numerical inputs in the demonstrations are assumptions for the stated model. Normalized variables are dimensionless. The examples define their own geometry, excitation and measurement boundary.

Define the forward model, the measurement noise and the allowed parameter set before calculating the posterior. Then use the remaining ambiguity to choose the next informative measurement.

Put physical constraints into the candidate set

A prior should represent available engineering knowledge: dimensions, material ranges, known connections and parameters established by separate evidence. Positive capacitances and resistances, an admissible inductance matrix and the declared terminal topology should be respected in the candidate models.

Separate fixed parameters from uncertain ones. If an inductance is fixed from a design estimate, a posterior for capacitance is conditional on that estimate. Include uncertain fixture loads and calibration factors when they materially influence the response; otherwise the parameter fit can absorb setup error as a winding change.

Use the full complex response when its phase and uncertainty are available. If the retained observable is only a magnitude or a selected feature, calculate the likelihood for that observable. Information discarded during extraction does not return through the Bayesian calculation.

Make the likelihood reproducible

For a finite candidate set θ_k, Bayes’ rule gives:

P(θ_k | d) = P(d | θ_k)P(θ_k) / Σ_j P(d | θ_j)P(θ_j).

For a declared Gaussian scalar observation model with standard deviation σ, the likelihood is proportional to exp[−(d − g(θ_k))²/(2σ²)]. The normalization is common across candidates when σ is fixed.

When complex features are represented by real and imaginary components, retain their supported joint covariance. The discrete posterior below follows the explicitly assumed observation model and priors.

An unexplained systematic residual should prompt a review of the forward model and noise assumptions. Making σ very small without evidence can produce a concentrated posterior for an incomplete model.

An original positive-parameter example

Consider a parallel inductor and capacitor with a fixed nonnegative shunt conductance. Set L = 1 mH and allow C = 8, 10 or 12 nF with prior probabilities 0.25, 0.50 and 0.25. All three candidates are passive ideal networks.

At ω₀ = 1/sqrt(L C_ref), using C_ref = 10 nF, the frequency is 50.329 kHz. The susceptance is B = ω₀C − 1/(ω₀L). Normalize it as z = B/(ω₀C_ref) = C/C_ref − 1.

The three signed predictions are −0.2, 0 and +0.2. Suppose the first retained measurement uses only r = |z|, with observed r = 0.20 and independent Gaussian scalar noise σ_r = 0.05. The outer two candidates fit equally well; the middle candidate has a likelihood factor exp(−8).

Capacitance candidatePrior probabilityPosterior after magnitude observation
8 nF25.000%49.983%
10 nF50.000%0.034%
12 nF25.000%49.983%

The posterior mean remains exactly 10 nF by symmetry, even though the 10 nF candidate now has only about 0.034% probability. Reporting that mean alone would conceal the two surviving explanations.

The capacitance variance also increases from 2.000 nF² in the prior to approximately 3.999 nF² in this posterior. Updating need not decrease every variance: this observation eliminates the central candidate and leaves two separated alternatives.

Prior and two posterior probability distributions for eight, ten and twelve nanofarad candidates, showing unresolved magnitude modes and a signed-observation update.
Original three-candidate Bayesian update. A magnitude observation leaves two modes while the posterior mean remains at the almost eliminated middle candidate. A separate signed observation supplies discriminating information; all weights depend on the declared finite candidate set and noise model.

Add an independent signed observation

Now make a separate acquisition that preserves the sign of the normalized susceptance. In this example its observation is z_obs = 0.10, with σ_z = 0.12, and its noise is assumed independent of the first acquisition.

Multiply each first-stage probability by its signed-observation likelihood and normalize again. The resulting candidate probabilities are approximately 5.850% for 8 nF, 0.063% for 10 nF and 94.087% for 12 nF. The signed observation favors the positive-susceptance branch that the first magnitude observation could not distinguish.

Independence is tied to the separate acquisitions in this constructed calculation. Taking the absolute value and the sign from the same noisy response would generally require a joint observation model; counting them as independent measurements would reuse information.

The inference is confined to the three declared candidates and fixed L. It is not a continuous capacitance estimate or a measurement of a real winding. A wider candidate set or uncertain L can produce a different posterior structure.

Decide from the posterior, then test its predictions

Retain candidate weights, likelihood assumptions and forward-response predictions in the handover. If a posterior has several modes, report those alternatives rather than compressing them into a mean and a symmetric interval that crosses an unsupported region.

Check how the conclusion changes with a defensible alternative prior, a larger noise estimate and additional uncertain parameters. Compare posterior predictions against a response not used in the update. A candidate that fits the retained feature but fails that independent response needs revision.

Connect the posterior to the engineering action: state which models the current data separate, which additional port or phase-sensitive response supplies information, and how the conclusion changes across justified assumptions. Retain the candidate predictions and weights with that measurement decision.

NIST TN 1297 provides the measurement-uncertainty basis for retaining influence quantities and covariance. Apply that bookkeeping to the declared inputs and comparison metric rather than treating numerical agreement as a measurement uncertainty. [1]

Gustavsen and Heitz show that fitted multiport accuracy depends on terminal conditions and the visibility of small modes. Validate the response used for the engineering decision under its actual terminal loads. [2]

References

[1] Barry N. Taylor and Chris E. Kuyatt, NIST Technical Note 1297, Guidelines for Evaluating and Expressing the Uncertainty of NIST Measurement Results, 1994.

[2] B. Gustavsen and C. Heitz, Modal Vector Fitting: A Tool for Generating Rational Models of High Accuracy with Arbitrary Terminal Conditions, 2008, DOI:10.1109/TADVP.2008.927810.

Chenfan Electric