Chenfan Electric
EN
Send drawing

ARTICLETechnical article

Effective GIC from Autotransformer Series and Common Windings

  • Chenfan Power

Quasi-DC current follows the conductive series and common-winding paths of an autotransformer. Effective GIC combines their signed ampere-turn contributions. Use the physical branch currents and turns relationship to define the equivalent magnetic input. [1]

Draw the actual DC circuit first. Define Is positive through the series winding from the high terminal toward the low terminal, and Ic positive through the common winding from the low terminal toward neutral. Use winding polarity compatible with that series-plus-common definition.

Effective GIC from Autotransformer Series and Common Windings: technical review table
Recalculate a signed example

Refer both winding contributions to the same turns

Let Ns and Nc be series and common turns. The signed DC magnetomotive force is Fdc = NsIs + NcIc in ampere-turns. Refer it to the complete high-voltage turns NH = Ns + Nc, defining Ieq = Fdc/NH in amperes. This is a magnetic-current reference definition, not another physical conductor.

With k = Nc/NH, Ieq = (1 − k)Is + kIc. For the ideal voltage ratio corresponding to this winding arrangement, k ≈ VX/VH, using compatible rated RMS terminal voltages. If the three common phase paths are equal, Ic = IN/3 and Is is the high-side phase DC current IH.

The result is Ieq = IH + (IN/3 − IH)(VX/VH), matching the historical NERC white-paper expression under these definitions. Different current directions require their signs to be changed consistently before using it. [1]

Recalculate a signed example

Illustrative inputValueMagnetic contribution
Common/full-HV turns ratio k0.5Both weighting factors equal 0.5
Series phase current Is+5 A+2.5 A on the full-HV-turn basis
Neutral current IN+60 AIc = +20 A; contribution +10 A
Effective current Ieq+12.5 ASum of the two referred contributions

These assumed currents are not network predictions or equipment capability data. Their purpose is to expose the weighting. Using IN/3 alone would give 20 A, while using IH alone would give 5 A; neither equals the defined effective input. [2]

Keep the DC path model separate from the magnetic reduction

Winding DC resistances and station grounding determine Is and Ic through the connected network. The turns-weighted reduction then supplies an input to a magnetic or thermal assessment. It cannot replace the DC network that calculated the branch currents.

For unequal phase paths, derive each phase’s signed winding contribution before selecting an aggregate model input. A cancelling station neutral total does not prove zero DC ampere-turns in every phase or series winding.

Keep Is, Ic, the turns ratio and reference directions beside Ieq. Use the equivalent current for the defined magnetic comparison and the actual branch currents for conductor-loss and local-heating calculations.

References

  1. NERC, Transformer Thermal Impact Assessment White Paper, Project 2013-03 Geomagnetic Disturbance Mitigation, October 2017.
  2. R. L. Bailey and coauthors, Modelling geomagnetically induced currents in midlatitude Central Europe using a thin-sheet approach, Annales Geophysicae 35, 2017. DOI: 10.5194/angeo-35-751-2017.
Chenfan Electric

Direct coordination

Start a conversation.

A drawing, a material requirement, or a project to discuss.

Send drawing