A coil tuned at modest neutral voltage can show a different effective compensation response during an earth fault. Magnetic nonlinearity, voltage amplitude and waveform distortion determine that change. Evaluate the electrical response over the neutral-voltage range that matters to the application.
The regulator manual includes coil-position linearization [1]; that function does not establish voltage-independent compensation. Compare the actual coil at stated voltage, frequency, temperature, position and magnetic history, with the source waveform recorded.

Define the inductance quantity used in each measurement
Flux linkage λ has units of volt-seconds. For an identified coil port, dλ/dt = v − Ri in a lumped model that assigns the relevant linked flux to λ. Instantaneous voltage v is volts, current i is amperes, resistance R is ohms and time is seconds.
A secant inductance λ/i and an incremental inductance dλ/di answer different questions. Their equality requires a suitable linear relation. A fundamental equivalent inferred from the complex voltage and current at one frequency is another representation; it can hide harmonic current and hysteretic behavior.
| Parameter | Useful question | Limit |
|---|---|---|
| Secant λ/i | Flux-linkage relation at an identified state | Depends on magnetic history and the chosen origin |
| Incremental dλ/di | Local response to a small change | Does not represent the entire cycle |
| Fundamental port admittance | Compensation at the measured sinusoidal condition | Does not describe harmonic current alone |
| Full voltage/current waveform | Cycle distortion and transient demand | Requires a validated measurement or nonlinear model |
Compare the response at matched mechanical position
Use a voltage-dependent record at each relevant position rather than one scalar inductance. Retain the fundamental current’s active and reactive components, harmonic spectrum and actual voltage distortion. A distorted source voltage can create current harmonics even without the magnetic mechanism being investigated.
In an elementary inductive model, lower effective inductance at unchanged voltage increases the lagging fundamental current. That can shift compensation toward the overcompensated side under a defined sign convention. The actual coil’s loss and distortion may change simultaneously, so the full admittance and waveform remain necessary.
Compare the neutral-network response using the coil behavior at the appropriate amplitude. If a grounding transformer is in the series path, its own amplitude-dependent contribution also belongs in the model. Fitting all observed change to the coil can assign a transformer effect to the wrong component.
Track the tuning consequence separately from the withstand question
Plot effective compensation against applied neutral voltage and mark the measurement uncertainty. Then examine how that curve changes the network’s mismatch and recovery response. Thermal and insulation limits are separate equipment questions; a satisfactory compensation point does not prove either one.
Compare low-voltage tuning with the fault-voltage response
Assumptions: at 50 Hz the coil’s measured fundamental equivalent is 1.00 H at 5.0 kV RMS, but 0.80 H at 10.0 kV RMS at the same mechanical position. Neglect resistance solely for this screen. Currents are 15.92 A and 39.79 A. Scaling the low-voltage result linearly predicts only 31.83 A at 10.0 kV, understating the assumed high-amplitude current by 7.96 A or 20% of its actual value. Characterize the port over the required amplitude before crediting the tuning range [1] [2]; waveform distortion and losses require their own measured components.
Characterise the voltage-dependent response at the relevant positions, with magnetic history and waveform distortion recorded. Use those results to establish the compensation range at high neutral voltage and the controller information needed to reach it.
References
- A. Eberle GmbH & Co. KG, The Petersen-Coil Regulator, REG-DP/REG-DPA, including Current Injection and High Power Current Injection, Operating Instructions, April 2017.
- U.S. Department of Energy, DOE-HDBK-1011/3-92, Electrical Science, Volume 3, June 1992.